Guide / feeders / NEC 2023
Subpanel wire size
A 100 A subpanel needs at least 3 AWG copper or 1 AWG aluminum. A 60 A subpanel needs 6 AWG copper or 4 AWG aluminum.
Feeder at full rating, 75 C terminations, 30 C ambient, runs short enough that voltage drop stays under 3%. Subpanel feeders never use the 83% dwelling service rule.
Subpanel wire size chart
| Feeder breaker | Copper, NM-B (60 C) | Copper, 75 C | Aluminum, 75 C | Ground wire |
|---|---|---|---|---|
| 30 A | 10 AWG | 10 AWG | 8 AWG | 10 AWG Cu / 8 AWG Al |
| 40 A | 8 AWG | 8 AWG | 8 AWG | 10 AWG Cu / 8 AWG Al |
| 50 A | 6 AWG | 8 AWG | 6 AWG | 10 AWG Cu / 8 AWG Al |
| 60 A | 4 AWG | 6 AWG | 4 AWG | 10 AWG Cu / 8 AWG Al |
| 70 A | 4 AWG | 4 AWG | 3 AWG | 8 AWG Cu / 6 AWG Al |
| 80 A | 3 AWG | 4 AWG | 2 AWG | 8 AWG Cu / 6 AWG Al |
| 90 A | 2 AWG | 3 AWG | 2 AWG | 8 AWG Cu / 6 AWG Al |
| 100 A | 1 AWG | 3 AWG | 1 AWG | 8 AWG Cu / 6 AWG Al |
| 125 A | - | 1 AWG | 2/0 AWG | 6 AWG Cu / 4 AWG Al |
| 150 A | - | 1/0 AWG | 3/0 AWG | 6 AWG Cu / 4 AWG Al |
| 200 A | - | 3/0 AWG | 250 kcmil | 6 AWG Cu / 4 AWG Al |
Subpanel wire size by distance
Minimum size at full load to stay at or under 3% voltage drop, 240 V. Distance is one way from the main panel.
| Feeder | 50 ft | 100 ft | 150 ft | 200 ft |
|---|---|---|---|---|
| 60 A copper | 6 AWG | 6 AWG | 4 AWG | 3 AWG |
| 60 A aluminum | 4 AWG | 4 AWG | 3 AWG | 1 AWG |
| 100 A copper | 3 AWG | 3 AWG | 3 AWG | 1 AWG |
| 100 A aluminum | 1 AWG | 1 AWG | 1/0 AWG | 2/0 AWG |
How to wire a subpanel feeder
- Four conductors: two hots, a neutral and an equipment ground. The neutral and ground stay separate at the subpanel.
- Neutral bar isolated: remove or leave out the bonding screw or strap in the subpanel. Neutral and ground are bonded only at the service.
- Ground sized by the feeder breaker: from NEC Table 250.122, shown in the chart above.
- Detached buildings: add a grounding electrode system at the building (NEC 250.32) and a disconnect if the subpanel's main breaker does not serve as one.
- Aluminum feeders: use lugs marked AL/CU, antioxidant compound where the lug maker calls for it, and torque to the label value (NEC 110.14(D)).
Calculator
Size your subpanel feeder
Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate
Permit and inspection: adding a subpanel is a feeder installation, which most jurisdictions require a permit for. A load calculation under NEC Article 220 decides the feeder size; this page assumes you already know the breaker you need.
Subpanel questions
What size wire for a 100 amp subpanel?
At full rating with 75 C terminations: 3 AWG copper or 1 AWG aluminum, plus an 8 AWG copper or 6 AWG aluminum ground. The 83% dwelling rule does not apply to subpanel feeders.
What size wire for a 60 amp subpanel?
6 AWG copper or 4 AWG aluminum at 75 C, with a 10 AWG copper or 8 AWG aluminum ground. In NM-B cable, use 4 AWG copper because NM-B is held to the 60 C column.
Does a subpanel need 4 wires?
Yes. A subpanel needs two hots, a neutral and a separate equipment ground. In the subpanel, the neutral bar stays isolated from the enclosure and the ground bar is bonded to it.
Can I use 2-2-2-4 aluminum for a 100 amp subpanel?
2 AWG aluminum is rated 90 A at 75 C, so on a feeder that needs the full 100 A it is too small. It suits a 90 A breaker, or a dwelling main service under the 83% rule.
Does a detached garage subpanel need a ground rod?
Yes. A feeder to a separate building needs its own grounding electrode system at that building (NEC 250.32), in addition to the equipment ground run with the feeder.