Guide / feeders / NEC 2023

Subpanel wire size

A 100 A subpanel needs at least 3 AWG copper or 1 AWG aluminum. A 60 A subpanel needs 6 AWG copper or 4 AWG aluminum.

Feeder at full rating, 75 C terminations, 30 C ambient, runs short enough that voltage drop stays under 3%. Subpanel feeders never use the 83% dwelling service rule.

Subpanel wire size chart

Feeder breakerCopper, NM-B (60 C)Copper, 75 CAluminum, 75 CGround wire
30 A10 AWG10 AWG8 AWG10 AWG Cu / 8 AWG Al
40 A8 AWG8 AWG8 AWG10 AWG Cu / 8 AWG Al
50 A6 AWG8 AWG6 AWG10 AWG Cu / 8 AWG Al
60 A4 AWG6 AWG4 AWG10 AWG Cu / 8 AWG Al
70 A4 AWG4 AWG3 AWG8 AWG Cu / 6 AWG Al
80 A3 AWG4 AWG2 AWG8 AWG Cu / 6 AWG Al
90 A2 AWG3 AWG2 AWG8 AWG Cu / 6 AWG Al
100 A1 AWG3 AWG1 AWG8 AWG Cu / 6 AWG Al
125 A-1 AWG2/0 AWG6 AWG Cu / 4 AWG Al
150 A-1/0 AWG3/0 AWG6 AWG Cu / 4 AWG Al
200 A-3/0 AWG250 kcmil6 AWG Cu / 4 AWG Al
NEC 2023 Table 310.16 and 240.4(D) for the feeder, Table 250.122 for the ground. NM-B shown up to 100 A. Most subpanel breakers and lugs are rated 75 C; check the labels.

Subpanel wire size by distance

Minimum size at full load to stay at or under 3% voltage drop, 240 V. Distance is one way from the main panel.

Feeder50 ft100 ft150 ft200 ft
60 A copper6 AWG6 AWG4 AWG3 AWG
60 A aluminum4 AWG4 AWG3 AWG1 AWG
100 A copper3 AWG3 AWG3 AWG1 AWG
100 A aluminum1 AWG1 AWG1/0 AWG2/0 AWG
Full-load sizing is conservative: a subpanel rarely runs at its breaker rating for long. Run your real load in the calculator below.

How to wire a subpanel feeder

Calculator

Size your subpanel feeder

A
V
System
Conductor
Max voltage drop
Wire type
Terminals rated
Hot locations and bundled wires
°C
in run

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

Permit and inspection: adding a subpanel is a feeder installation, which most jurisdictions require a permit for. A load calculation under NEC Article 220 decides the feeder size; this page assumes you already know the breaker you need.

Subpanel questions

What size wire for a 100 amp subpanel?

At full rating with 75 C terminations: 3 AWG copper or 1 AWG aluminum, plus an 8 AWG copper or 6 AWG aluminum ground. The 83% dwelling rule does not apply to subpanel feeders.

What size wire for a 60 amp subpanel?

6 AWG copper or 4 AWG aluminum at 75 C, with a 10 AWG copper or 8 AWG aluminum ground. In NM-B cable, use 4 AWG copper because NM-B is held to the 60 C column.

Does a subpanel need 4 wires?

Yes. A subpanel needs two hots, a neutral and a separate equipment ground. In the subpanel, the neutral bar stays isolated from the enclosure and the ground bar is bonded to it.

Can I use 2-2-2-4 aluminum for a 100 amp subpanel?

2 AWG aluminum is rated 90 A at 75 C, so on a feeder that needs the full 100 A it is too small. It suits a 90 A breaker, or a dwelling main service under the 83% rule.

Does a detached garage subpanel need a ground rod?

Yes. A feeder to a separate building needs its own grounding electrode system at that building (NEC 250.32), in addition to the equipment ground run with the feeder.