Chart 04 / ASTM B258 / 4/0 to 40
Wire Gauge Chart
Every American Wire Gauge size from 4/0 to 40, with the physical size, copper resistance and, for building wire, how many amps it carries.
| AWG | Diameter (in) | Diameter (mm) | Area (cmil) | Area (mm²) | Ohm/1000 ft | Amps 60 C | Amps 75 C |
|---|---|---|---|---|---|---|---|
| 4/0 | 0.46 | 11.684 | 211,600 | 107.219 | 0.049 | 195 | 230 |
| 3/0 | 0.4096 | 10.405 | 167,806 | 85.029 | 0.0618 | 165 | 200 |
| 2/0 | 0.3648 | 9.266 | 133,077 | 67.431 | 0.0779 | 145 | 175 |
| 1/0 | 0.3249 | 8.251 | 105,535 | 53.475 | 0.0983 | 125 | 150 |
| 1 | 0.2893 | 7.348 | 83,693 | 42.408 | 0.1239 | 110 | 130 |
| 2 | 0.2576 | 6.544 | 66,371 | 33.631 | 0.1563 | 95 | 115 |
| 3 | 0.2294 | 5.827 | 52,635 | 26.67 | 0.197 | 85 | 100 |
| 4 | 0.2043 | 5.189 | 41,741 | 21.151 | 0.2485 | 70 | 85 |
| 5 | 0.1819 | 4.621 | 33,102 | 16.773 | 0.3133 | - | - |
| 6 | 0.162 | 4.115 | 26,251 | 13.302 | 0.3951 | 55 | 65 |
| 7 | 0.1443 | 3.665 | 20,818 | 10.549 | 0.4982 | - | - |
| 8 | 0.1285 | 3.264 | 16,510 | 8.366 | 0.6282 | 40 | 50 |
| 9 | 0.1144 | 2.906 | 13,093 | 6.634 | 0.7921 | - | - |
| 10 | 0.1019 | 2.588 | 10,383 | 5.261 | 0.9988 | 30 | 35 |
| 11 | 0.0907 | 2.305 | 8,234 | 4.172 | 1.26 | - | - |
| 12 | 0.0808 | 2.053 | 6,530 | 3.309 | 1.59 | 20 | 25 |
| 13 | 0.072 | 1.828 | 5,178 | 2.624 | 2 | - | - |
| 14 | 0.0641 | 1.628 | 4,107 | 2.081 | 2.53 | 15 | 20 |
| 15 | 0.0571 | 1.45 | 3,257 | 1.65 | 3.18 | - | - |
| 16 | 0.0508 | 1.291 | 2,583 | 1.309 | 4.02 | - | - |
| 17 | 0.0453 | 1.15 | 2,048 | 1.038 | 5.06 | - | - |
| 18 | 0.0403 | 1.024 | 1,624 | 0.823 | 6.38 | - | - |
| 19 | 0.0359 | 0.912 | 1,288 | 0.653 | 8.05 | - | - |
| 20 | 0.032 | 0.812 | 1,022 | 0.518 | 10.15 | - | - |
| 21 | 0.0285 | 0.723 | 810 | 0.41 | 12.8 | - | - |
| 22 | 0.0253 | 0.644 | 642 | 0.326 | 16.14 | - | - |
| 23 | 0.0226 | 0.573 | 509 | 0.258 | 20.36 | - | - |
| 24 | 0.0201 | 0.511 | 404 | 0.205 | 25.67 | - | - |
| 25 | 0.0179 | 0.455 | 320 | 0.162 | 32.37 | - | - |
| 26 | 0.0159 | 0.405 | 254 | 0.129 | 40.81 | - | - |
| 27 | 0.0142 | 0.361 | 202 | 0.102 | 51.47 | - | - |
| 28 | 0.0126 | 0.321 | 160 | 0.081 | 64.9 | - | - |
| 29 | 0.0113 | 0.286 | 127 | 0.0642 | 81.83 | - | - |
| 30 | 0.01 | 0.255 | 101 | 0.0509 | 103.19 | - | - |
| 31 | 0.0089 | 0.227 | 79.7 | 0.0404 | 130.12 | - | - |
| 32 | 0.008 | 0.202 | 63.21 | 0.032 | 164.08 | - | - |
| 33 | 0.0071 | 0.18 | 50.13 | 0.0254 | 206.9 | - | - |
| 34 | 0.0063 | 0.16 | 39.75 | 0.0201 | 260.9 | - | - |
| 35 | 0.0056 | 0.143 | 31.52 | 0.016 | 328.98 | - | - |
| 36 | 0.005 | 0.127 | 25 | 0.0127 | 414.84 | - | - |
| 37 | 0.0045 | 0.113 | 19.83 | 0.01 | 523.1 | - | - |
| 38 | 0.004 | 0.101 | 15.72 | 0.008 | 659.62 | - | - |
| 39 | 0.0035 | 0.09 | 12.47 | 0.0063 | 831.77 | - | - |
| 40 | 0.0031 | 0.08 | 9.89 | 0.005 | 1,048.84 | - | - |
How AWG sizes are defined
AWG sizes follow a fixed geometric series (ASTM B258). The diameter of gauge n is 0.127 mm × 92(36 − n)/39, so 36 AWG is exactly 0.005 in and 4/0 is 0.46 in. From the diameter you get the area, and from the area and the resistivity of copper you get the resistance. Every value on this page is calculated from that formula, which is why it matches manufacturer tables to three or four significant figures.
Need metric sizes? Use the AWG to mm² converter. Need to know which size to buy? Use the wire size calculator or the wire size chart by amps.
Wire gauge questions
Why do bigger AWG numbers mean thinner wire?
AWG came from wire drawing: each number was one more pass through a smaller die. Every 3 gauges halves the area and every 6 gauges halves the diameter, roughly.
What do 1/0, 2/0, 3/0 and 4/0 mean?
Sizes larger than 1 AWG continue as 0, 00, 000 and 0000, written 1/0 to 4/0 and spoken "one aught" to "four aught". Above 4/0, sizes are given in kcmil (thousands of circular mils), starting at 250 kcmil.
Is gauge the same as diameter of stranded wire?
The AWG size describes the copper area. Stranded wire of the same gauge has the same area but a slightly larger overall diameter because of the gaps between strands.