Chart 04 / ASTM B258 / 4/0 to 40

Wire Gauge Chart

Every American Wire Gauge size from 4/0 to 40, with the physical size, copper resistance and, for building wire, how many amps it carries.

AWGDiameter (in)Diameter (mm)Area (cmil)Area (mm²)Ohm/1000 ftAmps 60 CAmps 75 C
4/0 0.46 11.684 211,600 107.219 0.049 195 230
3/0 0.4096 10.405 167,806 85.029 0.0618 165 200
2/0 0.3648 9.266 133,077 67.431 0.0779 145 175
1/0 0.3249 8.251 105,535 53.475 0.0983 125 150
1 0.2893 7.348 83,693 42.408 0.1239 110 130
2 0.2576 6.544 66,371 33.631 0.1563 95 115
3 0.2294 5.827 52,635 26.67 0.197 85 100
4 0.2043 5.189 41,741 21.151 0.2485 70 85
5 0.1819 4.621 33,102 16.773 0.3133 - -
6 0.162 4.115 26,251 13.302 0.3951 55 65
7 0.1443 3.665 20,818 10.549 0.4982 - -
8 0.1285 3.264 16,510 8.366 0.6282 40 50
9 0.1144 2.906 13,093 6.634 0.7921 - -
10 0.1019 2.588 10,383 5.261 0.9988 30 35
11 0.0907 2.305 8,234 4.172 1.26 - -
12 0.0808 2.053 6,530 3.309 1.59 20 25
13 0.072 1.828 5,178 2.624 2 - -
14 0.0641 1.628 4,107 2.081 2.53 15 20
15 0.0571 1.45 3,257 1.65 3.18 - -
16 0.0508 1.291 2,583 1.309 4.02 - -
17 0.0453 1.15 2,048 1.038 5.06 - -
18 0.0403 1.024 1,624 0.823 6.38 - -
19 0.0359 0.912 1,288 0.653 8.05 - -
20 0.032 0.812 1,022 0.518 10.15 - -
21 0.0285 0.723 810 0.41 12.8 - -
22 0.0253 0.644 642 0.326 16.14 - -
23 0.0226 0.573 509 0.258 20.36 - -
24 0.0201 0.511 404 0.205 25.67 - -
25 0.0179 0.455 320 0.162 32.37 - -
26 0.0159 0.405 254 0.129 40.81 - -
27 0.0142 0.361 202 0.102 51.47 - -
28 0.0126 0.321 160 0.081 64.9 - -
29 0.0113 0.286 127 0.0642 81.83 - -
30 0.01 0.255 101 0.0509 103.19 - -
31 0.0089 0.227 79.7 0.0404 130.12 - -
32 0.008 0.202 63.21 0.032 164.08 - -
33 0.0071 0.18 50.13 0.0254 206.9 - -
34 0.0063 0.16 39.75 0.0201 260.9 - -
35 0.0056 0.143 31.52 0.016 328.98 - -
36 0.005 0.127 25 0.0127 414.84 - -
37 0.0045 0.113 19.83 0.01 523.1 - -
38 0.004 0.101 15.72 0.008 659.62 - -
39 0.0035 0.09 12.47 0.0063 831.77 - -
40 0.0031 0.08 9.89 0.005 1,048.84 - -
Solid copper, resistance at 20 C. Ampacity for copper building wire from NEC 2023 Table 310.16; small sizes are also limited by NEC 240.4(D) (14 AWG 15 A, 12 AWG 20 A, 10 AWG 30 A). Sizes below 14 AWG are not used for branch circuits.

How AWG sizes are defined

AWG sizes follow a fixed geometric series (ASTM B258). The diameter of gauge n is 0.127 mm × 92(36 − n)/39, so 36 AWG is exactly 0.005 in and 4/0 is 0.46 in. From the diameter you get the area, and from the area and the resistivity of copper you get the resistance. Every value on this page is calculated from that formula, which is why it matches manufacturer tables to three or four significant figures.

Need metric sizes? Use the AWG to mm² converter. Need to know which size to buy? Use the wire size calculator or the wire size chart by amps.

Wire gauge questions

Why do bigger AWG numbers mean thinner wire?

AWG came from wire drawing: each number was one more pass through a smaller die. Every 3 gauges halves the area and every 6 gauges halves the diameter, roughly.

What do 1/0, 2/0, 3/0 and 4/0 mean?

Sizes larger than 1 AWG continue as 0, 00, 000 and 0000, written 1/0 to 4/0 and spoken "one aught" to "four aught". Above 4/0, sizes are given in kcmil (thousands of circular mils), starting at 250 kcmil.

Is gauge the same as diameter of stranded wire?

The AWG size describes the copper area. Stranded wire of the same gauge has the same area but a slightly larger overall diameter because of the gaps between strands.