Chart 05 / 15 to 400 A
Wire Size Chart by Amps
The minimum wire for each standard breaker size, in copper and aluminum. Start here, then check voltage drop if the run is long.
| Breaker | Copper NM-B (60 C) | Copper THHN (75 C) | Aluminum (75 C) |
|---|---|---|---|
| 15 A | 14 AWG | 14 AWG | 12 AWG |
| 20 A | 12 AWG | 12 AWG | 10 AWG |
| 25 A | 10 AWG | 10 AWG | 10 AWG |
| 30 A | 10 AWG | 10 AWG | 8 AWG |
| 35 A | 8 AWG | 8 AWG | 8 AWG |
| 40 A | 8 AWG | 8 AWG | 8 AWG |
| 45 A | 6 AWG | 8 AWG | 6 AWG |
| 50 A | 6 AWG | 8 AWG | 6 AWG |
| 60 A | 4 AWG | 6 AWG | 4 AWG |
| 70 A | 4 AWG | 4 AWG | 3 AWG |
| 80 A | 3 AWG | 4 AWG | 2 AWG |
| 90 A | 2 AWG | 3 AWG | 2 AWG |
| 100 A | 1 AWG | 3 AWG | 1 AWG |
| 110 A | - | 2 AWG | 1/0 AWG |
| 125 A | - | 1 AWG | 2/0 AWG |
| 150 A | - | 1/0 AWG | 3/0 AWG |
| 175 A | - | 2/0 AWG | 4/0 AWG |
| 200 A | - | 3/0 AWG | 250 kcmil |
| 225 A | - | 4/0 AWG | 300 kcmil |
| 250 A | - | 250 kcmil | 350 kcmil |
| 300 A | - | 350 kcmil | 500 kcmil |
| 350 A | - | 500 kcmil | 700 kcmil |
| 400 A | - | 600 kcmil | 900 kcmil |
Dwelling service and main feeder sizes
| Service | Copper | Aluminum |
|---|---|---|
| 100 A | 4 AWG | 2 AWG |
| 125 A | 2 AWG | 1/0 AWG |
| 150 A | 1 AWG | 2/0 AWG |
| 200 A | 2/0 AWG | 4/0 AWG |
| 225 A | 3/0 AWG | 250 kcmil |
| 300 A | 250 kcmil | 350 kcmil |
| 400 A | 400 kcmil | 600 kcmil |
Detailed guides by amps
Calculator
Size for your exact run
Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate
Wire size chart questions
Why are there two copper columns?
NM-B cable is limited to the 60 C ampacity column, and so are most circuits of 100 A or less unless every terminal is rated 75 C. THHN conductors in conduit with 75 C terminals can use the higher 75 C column, so they are sometimes one size smaller.
Does this chart include voltage drop?
No. It is the minimum size for the breaker. Long runs need a larger size; the amps pages show upsizing at 50 to 200 ft and the calculator handles any length.
Why are service sizes smaller than feeder sizes?
NEC 310.12 lets the service or main feeder of a dwelling use conductors rated at 83% of the service, because a home rarely draws its full service rating for long.