Service / 100 A / NEC 310.12

Wire size for 100 amp service

For a 100 A home service, use at least 4 AWG copper or 2 AWG aluminum. Where the full 100 A rating is needed, use 3 AWG copper or 1 AWG aluminum.

100 A services are common in older and smaller homes, and the code minimum wire is smaller than many people expect because of the dwelling 83% rule.

NEC 2023 310.12 and Table 310.16, 75 C column, 30 C ambient.

100 amp service wire sizes

UseRuleCopperAluminum
Dwelling service or main feeder83% of 100 A = 83 A4 AWG (85 A)2 AWG (90 A)
Subpanel feeder, non-dwelling serviceFull 100 A3 AWG (100 A)1 AWG (100 A)
Ampacity in brackets, 75 C column. Correct for ambient temperature and conductor count where they apply.

How the 83% rule works

NEC 310.12 covers one-family dwellings and the individual units of two-family and multifamily dwellings. The service-entrance conductors, or the main feeder that carries the whole load of the unit, may have an ampacity of 83% of the service rating. For 100 A that is 83 A, and the smallest conductors that reach it in the 75 C column are 4 AWG copper and 2 AWG aluminum.

The rule reflects how homes draw power: the whole-house load almost never sits at the service rating for long. It does not change the service size itself, which still comes from a load calculation under NEC Article 220.

Search results often say "3 AWG copper for 100 amp service". That is the full-rating answer (3 AWG copper is rated 100 A at 75 C). For a dwelling service, NEC 310.12 lets you use 4 AWG copper or 2 AWG aluminum.

If you plan to upgrade the service later, running larger conductors now (for example 2/0 aluminum in conduit) can save pulling new wire.

Grounding electrode conductor for 4 AWG copper or 2 AWG aluminum service conductors: 8 AWG copper or 6 AWG aluminum (NEC Table 250.66). Many inspectors expect 6 AWG copper where the GEC is exposed to damage.

Service work is for a licensed electrician. It needs a permit, an inspection and coordination with your utility, and it cannot be turned off at your own panel. Use this page to check a quote or plan an upgrade.

100 amp service questions

Is 2 gauge aluminum good for 100 amp service?

Yes, for a dwelling service under NEC 310.12. 2 AWG aluminum is rated 90 A at 75 C, which covers the 83 A required for a 100 A service.

Can I use 4 gauge copper for 100 amp service?

For a dwelling service or main feeder, yes. 4 AWG copper is rated 85 A at 75 C, above the 83 A minimum.

What size wire for a 100 amp subpanel?

A subpanel feeder is not a main service, so use full rating: 3 AWG copper or 1 AWG aluminum at 75 C.