Service / 100 A / NEC 310.12
Wire size for 100 amp service
For a 100 A home service, use at least 4 AWG copper or 2 AWG aluminum. Where the full 100 A rating is needed, use 3 AWG copper or 1 AWG aluminum.
100 A services are common in older and smaller homes, and the code minimum wire is smaller than many people expect because of the dwelling 83% rule.
NEC 2023 310.12 and Table 310.16, 75 C column, 30 C ambient.
100 amp service wire sizes
| Use | Rule | Copper | Aluminum |
|---|---|---|---|
| Dwelling service or main feeder | 83% of 100 A = 83 A | 4 AWG (85 A) | 2 AWG (90 A) |
| Subpanel feeder, non-dwelling service | Full 100 A | 3 AWG (100 A) | 1 AWG (100 A) |
How the 83% rule works
NEC 310.12 covers one-family dwellings and the individual units of two-family and multifamily dwellings. The service-entrance conductors, or the main feeder that carries the whole load of the unit, may have an ampacity of 83% of the service rating. For 100 A that is 83 A, and the smallest conductors that reach it in the 75 C column are 4 AWG copper and 2 AWG aluminum.
The rule reflects how homes draw power: the whole-house load almost never sits at the service rating for long. It does not change the service size itself, which still comes from a load calculation under NEC Article 220.
Search results often say "3 AWG copper for 100 amp service". That is the full-rating answer (3 AWG copper is rated 100 A at 75 C). For a dwelling service, NEC 310.12 lets you use 4 AWG copper or 2 AWG aluminum.
If you plan to upgrade the service later, running larger conductors now (for example 2/0 aluminum in conduit) can save pulling new wire.
Grounding electrode conductor for 4 AWG copper or 2 AWG aluminum service conductors: 8 AWG copper or 6 AWG aluminum (NEC Table 250.66). Many inspectors expect 6 AWG copper where the GEC is exposed to damage.
Service work is for a licensed electrician. It needs a permit, an inspection and coordination with your utility, and it cannot be turned off at your own panel. Use this page to check a quote or plan an upgrade.
100 amp service questions
Is 2 gauge aluminum good for 100 amp service?
Yes, for a dwelling service under NEC 310.12. 2 AWG aluminum is rated 90 A at 75 C, which covers the 83 A required for a 100 A service.
Can I use 4 gauge copper for 100 amp service?
For a dwelling service or main feeder, yes. 4 AWG copper is rated 85 A at 75 C, above the 83 A minimum.
What size wire for a 100 amp subpanel?
A subpanel feeder is not a main service, so use full rating: 3 AWG copper or 1 AWG aluminum at 75 C.
Related
- Wire size for 100 amps (feeders and circuits at full rating)
- Wire size for 200 amp service
- Ampacity chart