Chart 03 / Table 310.16 values

Wire Ampacity Chart

How many amps a wire can carry, by size, material and temperature rating. For house wiring, three pairs cover most circuits: 14 AWG on 15 A, 12 AWG on 20 A, 10 AWG on 30 A.

Common sizes

SizeCopperAluminumMax breaker
240.4(D)
60 C75 C90 C60 C75 C90 C
14 AWG 152025 --- Cu 15
12 AWG 202530 152025 Cu 20, Al 15
10 AWG 303540 253035 Cu 30, Al 25
8 AWG 405055 354045
6 AWG 556575 405055
4 AWG 708595 556575
3 AWG 85100115 657585
2 AWG 95115130 7590100
1 AWG 110130145 85100115
1/0 AWG 125150170 100120135
2/0 AWG 145175195 115135150
3/0 AWG 165200225 130155175
4/0 AWG 195230260 150180205
Amps. NEC 2023 Table 310.16 values, 30 C ambient, no more than three current-carrying conductors in a raceway or cable. Small-wire breaker limits from NEC 240.4(D).

Which column applies to you

60 C

NM-B (Romex) and UF-B cable, and any circuit of 100 A or less unless every terminal is listed for 75 C. This is the safe default for house wiring.

75 C

THHN, THWN, XHHW and SER conductors where the breaker and the equipment terminals are rated 75 C. Normal for feeders and services over 100 A.

90 C

THHN and XHHW-2 insulation rating. Used as the starting value when correcting for hot locations or many conductors together, never as the final answer above the terminal rating.

Full chart, 14 AWG to 1000 kcmil

SizeCopperAluminumMax breaker
240.4(D)
60 C75 C90 C60 C75 C90 C
18 AWG --14 --- Cu 7
16 AWG --18 --- Cu 10
14 AWG 152025 --- Cu 15
12 AWG 202530 152025 Cu 20, Al 15
10 AWG 303540 253035 Cu 30, Al 25
8 AWG 405055 354045
6 AWG 556575 405055
4 AWG 708595 556575
3 AWG 85100115 657585
2 AWG 95115130 7590100
1 AWG 110130145 85100115
1/0 AWG 125150170 100120135
2/0 AWG 145175195 115135150
3/0 AWG 165200225 130155175
4/0 AWG 195230260 150180205
250 kcmil 215255290 170205230
300 kcmil 240285320 195230260
350 kcmil 260310350 210250280
400 kcmil 280335380 225270305
500 kcmil 320380430 260310350
600 kcmil 350420475 285340385
700 kcmil 385460520 315375425
750 kcmil 400475535 320385435
800 kcmil 410490555 330395445
900 kcmil 435520585 355425480
1000 kcmil 455545615 375445500
Amps. A dash means the size is not listed for that material or temperature. See the NEC ampacity chart for correction and adjustment factors.

Calculator

Size a wire for your circuit

A
V
System
Conductor
Max voltage drop
Wire type
Hot locations and bundled wires
°C
in run

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

Ampacity questions

Which column of the ampacity chart should I use?

Use the lowest temperature rating of anything in the circuit: the wire insulation, the cable type and the terminals at both ends. NM-B cable and most residential breakers on circuits of 100 A or less put you in the 60 C column.

Why can 12 AWG copper only go on a 20 A breaker when the chart says 25 A?

NEC 240.4(D) caps the breaker for 14, 12 and 10 AWG copper at 15, 20 and 30 A. The higher chart values are used only as the starting point when you derate for heat or bundling.

What does the 90 C column mean?

It is the rating for 90 C insulation such as THHN. You can start derating from it, but the final ampacity cannot exceed the column of the terminals, usually 60 C or 75 C.