Chart 03 / Table 310.16 values
Wire Ampacity Chart
How many amps a wire can carry, by size, material and temperature rating. For house wiring, three pairs cover most circuits: 14 AWG on 15 A, 12 AWG on 20 A, 10 AWG on 30 A.
Common sizes
| Size | Copper | Aluminum | Max breaker 240.4(D) | ||||
|---|---|---|---|---|---|---|---|
| 60 C | 75 C | 90 C | 60 C | 75 C | 90 C | ||
| 14 AWG | 15 | 20 | 25 | - | - | - | Cu 15 |
| 12 AWG | 20 | 25 | 30 | 15 | 20 | 25 | Cu 20, Al 15 |
| 10 AWG | 30 | 35 | 40 | 25 | 30 | 35 | Cu 30, Al 25 |
| 8 AWG | 40 | 50 | 55 | 35 | 40 | 45 | |
| 6 AWG | 55 | 65 | 75 | 40 | 50 | 55 | |
| 4 AWG | 70 | 85 | 95 | 55 | 65 | 75 | |
| 3 AWG | 85 | 100 | 115 | 65 | 75 | 85 | |
| 2 AWG | 95 | 115 | 130 | 75 | 90 | 100 | |
| 1 AWG | 110 | 130 | 145 | 85 | 100 | 115 | |
| 1/0 AWG | 125 | 150 | 170 | 100 | 120 | 135 | |
| 2/0 AWG | 145 | 175 | 195 | 115 | 135 | 150 | |
| 3/0 AWG | 165 | 200 | 225 | 130 | 155 | 175 | |
| 4/0 AWG | 195 | 230 | 260 | 150 | 180 | 205 | |
Which column applies to you
60 C
NM-B (Romex) and UF-B cable, and any circuit of 100 A or less unless every terminal is listed for 75 C. This is the safe default for house wiring.
75 C
THHN, THWN, XHHW and SER conductors where the breaker and the equipment terminals are rated 75 C. Normal for feeders and services over 100 A.
90 C
THHN and XHHW-2 insulation rating. Used as the starting value when correcting for hot locations or many conductors together, never as the final answer above the terminal rating.
Full chart, 14 AWG to 1000 kcmil
| Size | Copper | Aluminum | Max breaker 240.4(D) | ||||
|---|---|---|---|---|---|---|---|
| 60 C | 75 C | 90 C | 60 C | 75 C | 90 C | ||
| 18 AWG | - | - | 14 | - | - | - | Cu 7 |
| 16 AWG | - | - | 18 | - | - | - | Cu 10 |
| 14 AWG | 15 | 20 | 25 | - | - | - | Cu 15 |
| 12 AWG | 20 | 25 | 30 | 15 | 20 | 25 | Cu 20, Al 15 |
| 10 AWG | 30 | 35 | 40 | 25 | 30 | 35 | Cu 30, Al 25 |
| 8 AWG | 40 | 50 | 55 | 35 | 40 | 45 | |
| 6 AWG | 55 | 65 | 75 | 40 | 50 | 55 | |
| 4 AWG | 70 | 85 | 95 | 55 | 65 | 75 | |
| 3 AWG | 85 | 100 | 115 | 65 | 75 | 85 | |
| 2 AWG | 95 | 115 | 130 | 75 | 90 | 100 | |
| 1 AWG | 110 | 130 | 145 | 85 | 100 | 115 | |
| 1/0 AWG | 125 | 150 | 170 | 100 | 120 | 135 | |
| 2/0 AWG | 145 | 175 | 195 | 115 | 135 | 150 | |
| 3/0 AWG | 165 | 200 | 225 | 130 | 155 | 175 | |
| 4/0 AWG | 195 | 230 | 260 | 150 | 180 | 205 | |
| 250 kcmil | 215 | 255 | 290 | 170 | 205 | 230 | |
| 300 kcmil | 240 | 285 | 320 | 195 | 230 | 260 | |
| 350 kcmil | 260 | 310 | 350 | 210 | 250 | 280 | |
| 400 kcmil | 280 | 335 | 380 | 225 | 270 | 305 | |
| 500 kcmil | 320 | 380 | 430 | 260 | 310 | 350 | |
| 600 kcmil | 350 | 420 | 475 | 285 | 340 | 385 | |
| 700 kcmil | 385 | 460 | 520 | 315 | 375 | 425 | |
| 750 kcmil | 400 | 475 | 535 | 320 | 385 | 435 | |
| 800 kcmil | 410 | 490 | 555 | 330 | 395 | 445 | |
| 900 kcmil | 435 | 520 | 585 | 355 | 425 | 480 | |
| 1000 kcmil | 455 | 545 | 615 | 375 | 445 | 500 | |
Calculator
Size a wire for your circuit
Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate
Ampacity questions
Which column of the ampacity chart should I use?
Use the lowest temperature rating of anything in the circuit: the wire insulation, the cable type and the terminals at both ends. NM-B cable and most residential breakers on circuits of 100 A or less put you in the 60 C column.
Why can 12 AWG copper only go on a 20 A breaker when the chart says 25 A?
NEC 240.4(D) caps the breaker for 14, 12 and 10 AWG copper at 15, 20 and 30 A. The higher chart values are used only as the starting point when you derate for heat or bundling.
What does the 90 C column mean?
It is the rating for 90 C insulation such as THHN. You can start derating from it, but the final ampacity cannot exceed the column of the terminals, usually 60 C or 75 C.