Gauge / 14 AWG / 1.63 mm
14 gauge wire
14 AWG copper is rated 15 A at 60 C, 20 A at 75 C and 25 A at 90 C. The breaker is limited to 15 A by NEC 240.4(D). Not listed in aluminum.
14 AWG copper is the smallest size allowed for general branch circuits in a home, and it belongs on a 15 A breaker.
Assumes NEC 2023 Table 310.16, 30 C ambient and no more than three current-carrying conductors. NM-B cable uses the 60 C column.
14 AWG specifications
| Diameter | 0.0641 in | 1.628 mm |
|---|---|---|
| Area | 4,107 cmil | 2.08 mm² |
| Copper resistance | 3.0712 ohm/1000 ft | 8.285 ohm/km |
| Aluminum resistance | 5.0576 ohm/1000 ft | 13.583 ohm/km |
| Copper weight | 12.4 lb/1000 ft | 18.5 kg/km |
| Nearest metric | 2.5 mm² | 2.5 mm² or larger |
NM-B cable: White sheath (14/2 and 14/3 NM-B).
14 AWG ampacity
| 60 C | 75 C | 90 C | Max breaker | |
|---|---|---|---|---|
| Copper | 15 | 20 | 25 | 15 |
| Aluminum | not listed | - | ||
What 14 gauge wire is used for
- 15 A general lighting circuits
- 15 A general-purpose receptacle circuits in bedrooms, living rooms and hallways
- Bathroom exhaust fans and light fixtures on a 15 A circuit
- Switch loops and fixture runs fed from a 15 A circuit
Table 310.16 lists 14 AWG copper at 15 A, 20 A and 25 A in the 60, 75 and 90 C columns, but NEC 240.4(D) caps the breaker at 15 A. The higher numbers are used only as the starting point for derating.
Kitchen countertop, bathroom receptacle and laundry circuits must be 20 A circuits in a dwelling, so 14 AWG is not an option there.
Over long runs, 14 AWG loses voltage fast. At a full 15 A on 120 V, it reaches 3% drop at about 39 ft one way.
How far can you run 14 gauge wire?
Longest one-way run in copper that keeps voltage drop at or below 3%, single-phase.
| Load | 120 V | 240 V |
|---|---|---|
| 5 A | 117 ft | 234 ft |
| 10 A | 59 ft | 117 ft |
| 15 A | 39 ft | 78 ft |
Check a run
Voltage drop on 14 AWG
Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate
14 gauge wire questions
Can I put 14 gauge wire on a 20 amp breaker?
No. NEC 240.4(D) limits 14 AWG copper to a 15 A overcurrent device. A 20 A breaker needs 12 AWG copper.
How many amps can 14 gauge wire handle?
15 A in normal house wiring. The 20 A and 25 A table values only matter when you apply derating for heat or bundling.
Is 14 gauge wire OK for outlets?
Yes, on a 15 A general-purpose receptacle circuit. Not for kitchen countertop, bathroom or laundry receptacle circuits, which must be 20 A.
Related sizes
Convert this size: AWG to mm². All sizes: wire gauge chart. Any size and length: voltage drop calculator. Cords: extension cord gauge chart. Audio: speaker wire gauge chart.