Gauge / 14 AWG / 1.63 mm

14 gauge wire

14 AWG copper is rated 15 A at 60 C, 20 A at 75 C and 25 A at 90 C. The breaker is limited to 15 A by NEC 240.4(D). Not listed in aluminum.

14 AWG copper is the smallest size allowed for general branch circuits in a home, and it belongs on a 15 A breaker.

Assumes NEC 2023 Table 310.16, 30 C ambient and no more than three current-carrying conductors. NM-B cable uses the 60 C column.

1 tick = 1 mm 1.63 mm
14 AWG Copper conductor and typical insulation, drawn to scale against a millimetre ruler.

14 AWG specifications

Diameter0.0641 in1.628 mm
Area4,107 cmil2.08 mm²
Copper resistance3.0712 ohm/1000 ft8.285 ohm/km
Aluminum resistance5.0576 ohm/1000 ft13.583 ohm/km
Copper weight12.4 lb/1000 ft18.5 kg/km
Nearest metric2.5 mm²2.5 mm² or larger
Solid conductor. Resistance per 1000 ft at 75 C, per km at 20 C. Stranded wire is about 2% higher.

NM-B cable: White sheath (14/2 and 14/3 NM-B).

14 AWG ampacity

60 C75 C90 CMax breaker
Copper15202515
Aluminumnot listed-
Amps. 60 C: NM-B, UF-B and most terminals on circuits of 100 A or less. 75 C: THHN/THWN with 75 C rated terminals. 90 C: for derating only.

What 14 gauge wire is used for

Table 310.16 lists 14 AWG copper at 15 A, 20 A and 25 A in the 60, 75 and 90 C columns, but NEC 240.4(D) caps the breaker at 15 A. The higher numbers are used only as the starting point for derating.

Kitchen countertop, bathroom receptacle and laundry circuits must be 20 A circuits in a dwelling, so 14 AWG is not an option there.

Over long runs, 14 AWG loses voltage fast. At a full 15 A on 120 V, it reaches 3% drop at about 39 ft one way.

How far can you run 14 gauge wire?

Longest one-way run in copper that keeps voltage drop at or below 3%, single-phase.

Load120 V240 V
5 A117 ft234 ft
10 A59 ft117 ft
15 A39 ft78 ft
Resistance at 75 C. Aluminum runs are about 40% shorter.

Check a run

Voltage drop on 14 AWG

A
V
System
Conductor

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

14 gauge wire questions

Can I put 14 gauge wire on a 20 amp breaker?

No. NEC 240.4(D) limits 14 AWG copper to a 15 A overcurrent device. A 20 A breaker needs 12 AWG copper.

How many amps can 14 gauge wire handle?

15 A in normal house wiring. The 20 A and 25 A table values only matter when you apply derating for heat or bundling.

Is 14 gauge wire OK for outlets?

Yes, on a 15 A general-purpose receptacle circuit. Not for kitchen countertop, bathroom or laundry receptacle circuits, which must be 20 A.

Related sizes

Convert this size: AWG to mm². All sizes: wire gauge chart. Any size and length: voltage drop calculator. Cords: extension cord gauge chart. Audio: speaker wire gauge chart.