Gauge / 10 AWG / 2.59 mm

10 gauge wire

10 AWG copper is rated 30 A at 60 C, 35 A at 75 C and 40 A at 90 C. The breaker is limited to 30 A by NEC 240.4(D). Aluminum: 25 / 30 / 35 A, 25 A breaker max.

10 AWG copper is the go-to size for 30 A circuits such as electric dryers and water heaters.

Assumes NEC 2023 Table 310.16, 30 C ambient and no more than three current-carrying conductors. NM-B cable uses the 60 C column.

1 tick = 1 mm 2.59 mm
10 AWG Copper conductor and typical insulation, drawn to scale against a millimetre ruler.

10 AWG specifications

Diameter0.1019 in2.588 mm
Area10,383 cmil5.26 mm²
Copper resistance1.2147 ohm/1000 ft3.277 ohm/km
Aluminum resistance2.0004 ohm/1000 ft5.372 ohm/km
Copper weight31.4 lb/1000 ft46.8 kg/km
Nearest metric6 mm²6 mm² or larger
Solid conductor. Resistance per 1000 ft at 75 C, per km at 20 C. Stranded wire is about 2% higher.

NM-B cable: Orange sheath (10/2 and 10/3 NM-B).

10 AWG ampacity

60 C75 C90 CMax breaker
Copper30354030
Aluminum25303525
Amps. 60 C: NM-B, UF-B and most terminals on circuits of 100 A or less. 75 C: THHN/THWN with 75 C rated terminals. 90 C: for derating only.

What 10 gauge wire is used for

NEC 240.4(D) limits 10 AWG copper to a 30 A breaker and 10 AWG aluminum to 25 A.

A 4,500 W water heater draws 18.75 A at 240 V. Water heaters are treated as continuous loads, so the circuit is sized at 125%: 23.4 A, which rounds up to a 25 A or 30 A breaker on 10 AWG.

Air conditioner nameplates list a minimum circuit ampacity and a maximum breaker. Use the nameplate, which can allow a larger breaker than 240.4(D) would normally permit for motor loads.

How far can you run 10 gauge wire?

Longest one-way run in copper that keeps voltage drop at or below 3%, single-phase.

Load120 V240 V
10 A148 ft296 ft
15 A99 ft198 ft
20 A74 ft148 ft
25 A59 ft119 ft
30 A49 ft99 ft
Resistance at 75 C. Aluminum runs are about 40% shorter.

Check a run

Voltage drop on 10 AWG

A
V
System
Conductor

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

10 gauge wire questions

How many amps can 10 gauge wire handle?

30 A on a standard circuit. Table 310.16 lists 30, 35 and 40 A for copper at 60, 75 and 90 C, but the breaker is capped at 30 A.

Is 10 gauge wire good for 40 amps?

No. A 40 A circuit needs 8 AWG copper.

What size wire for an electric dryer?

Most electric dryers use a 30 A, 240 V circuit with 10 AWG copper: 10/3 with ground for a 4-wire NEMA 14-30 outlet.

Related sizes

10 AWG copper is the minimum for: 30 amp circuits.

Convert this size: AWG to mm². All sizes: wire gauge chart. Any size and length: voltage drop calculator. Cords: extension cord gauge chart.