AWG to mm² Converter
Type an AWG size or a metric cross-section to convert both ways. Charts for every common size are below.
Converter
AWG ⇄ mm²
AWG to mm² chart
| AWG | mm² | Dia. mm | Nearest metric |
|---|---|---|---|
| 30 | 0.051 | 0.255 | 0.5 mm² |
| 28 | 0.081 | 0.321 | 0.5 mm² |
| 26 | 0.129 | 0.405 | 0.5 mm² |
| 24 | 0.205 | 0.511 | 0.5 mm² |
| 22 | 0.326 | 0.644 | 0.5 mm² |
| 20 | 0.518 | 0.812 | 0.5 mm² |
| 18 | 0.823 | 1.024 | 0.75 mm² |
| 16 | 1.309 | 1.291 | 1.5 mm² |
| 14 | 2.081 | 1.628 | 2.5 mm² |
| 12 | 3.309 | 2.053 | 4 mm² |
| 10 | 5.261 | 2.588 | 6 mm² |
| 8 | 8.366 | 3.264 | 10 mm² |
| 6 | 13.302 | 4.115 | 16 mm² |
| 4 | 21.151 | 5.189 | 25 mm² |
| 3 | 26.67 | 5.827 | 25 mm² |
| 2 | 33.631 | 6.544 | 35 mm² |
| 1 | 42.408 | 7.348 | 50 mm² |
| 1/0 | 53.475 | 8.251 | 50 mm² |
| 2/0 | 67.431 | 9.266 | 70 mm² |
| 3/0 | 85.029 | 10.405 | 95 mm² |
| 4/0 | 107.219 | 11.684 | 120 mm² |
mm² to AWG chart
| mm² | Nearest AWG | AWG, same or larger |
|---|---|---|
| 0.5 | 20 | 20 |
| 0.75 | 18 | 18 |
| 1 | 17 | 17 |
| 1.5 | 15 | 15 |
| 2.5 | 13 | 13 |
| 4 | 11 | 11 |
| 6 | 9 | 9 |
| 10 | 7 | 7 |
| 16 | 5 | 5 |
| 25 | 3 | 3 |
| 35 | 2 | 1 |
| 50 | 1/0 | 1/0 |
| 70 | 2/0 | 3/0 |
| 95 | 3/0 | 4/0 |
| 120 | 4/0 | - |
Why AWG and metric sizes do not line up
AWG is a geometric series where each step changes the diameter by a factor of about 1.123, so area changes by about 26% per gauge. IEC 60228 uses round preferred numbers (1.5, 2.5, 4, 6, 10 mm²). The two systems only coincide by accident, so a conversion is always "nearest" or "next size up". For current-carrying work, use the next size up.
Conversion questions
Is 2.5 mm² the same as 14 AWG?
No. 14 AWG is 2.08 mm², smaller than 2.5 mm². The nearest AWG to 2.5 mm² is 13 AWG (2.63 mm²), and the next common US size up is 12 AWG (3.31 mm²).
What AWG is 1.5 mm²?
1.5 mm² falls between 16 AWG (1.31 mm²) and 15 AWG (1.65 mm²). If you need at least the same copper, use 14 AWG in North American wiring, since 15 AWG is rarely sold.
Can I use the same current rating after converting?
Not directly. NEC and IEC or BS 7671 ratings differ and depend on installation method, so convert the size, then check the rating under the code that applies where the wire is installed.