Tool 06 / IEC 60228

AWG to mm² Converter

Type an AWG size or a metric cross-section to convert both ways. Charts for every common size are below.

Converter

AWG ⇄ mm²

AWG
mm²

Converts conductor size only. Current ratings differ between the NEC and IEC or BS 7671, and depend on how the cable is installed.

AWG to mm² chart

AWGmm²Dia. mmNearest metric
300.0510.2550.5 mm²
280.0810.3210.5 mm²
260.1290.4050.5 mm²
240.2050.5110.5 mm²
220.3260.6440.5 mm²
200.5180.8120.5 mm²
180.8231.0240.75 mm²
161.3091.2911.5 mm²
142.0811.6282.5 mm²
123.3092.0534 mm²
105.2612.5886 mm²
88.3663.26410 mm²
613.3024.11516 mm²
421.1515.18925 mm²
326.675.82725 mm²
233.6316.54435 mm²
142.4087.34850 mm²
1/053.4758.25150 mm²
2/067.4319.26670 mm²
3/085.02910.40595 mm²
4/0107.21911.684120 mm²

mm² to AWG chart

mm²Nearest AWGAWG, same or larger
0.52020
0.751818
11717
1.51515
2.51313
41111
699
1077
1655
2533
3521
501/01/0
702/03/0
953/04/0
1204/0-
Metric sizes from IEC 60228. "Same or larger" never gives you less copper than the metric size.

Why AWG and metric sizes do not line up

AWG is a geometric series where each step changes the diameter by a factor of about 1.123, so area changes by about 26% per gauge. IEC 60228 uses round preferred numbers (1.5, 2.5, 4, 6, 10 mm²). The two systems only coincide by accident, so a conversion is always "nearest" or "next size up". For current-carrying work, use the next size up.

Conversion questions

Is 2.5 mm² the same as 14 AWG?

No. 14 AWG is 2.08 mm², smaller than 2.5 mm². The nearest AWG to 2.5 mm² is 13 AWG (2.63 mm²), and the next common US size up is 12 AWG (3.31 mm²).

What AWG is 1.5 mm²?

1.5 mm² falls between 16 AWG (1.31 mm²) and 15 AWG (1.65 mm²). If you need at least the same copper, use 14 AWG in North American wiring, since 15 AWG is rarely sold.

Can I use the same current rating after converting?

Not directly. NEC and IEC or BS 7671 ratings differ and depend on installation method, so convert the size, then check the rating under the code that applies where the wire is installed.