Gauge / 1/0 AWG / 8.25 mm

1/0 gauge wire (0 AWG)

1/0 AWG copper is rated 125 A at 60 C, 150 A at 75 C and 170 A at 90 C. Aluminum: 100 / 120 / 135 A.

1/0 AWG copper is rated 150 A at 75 C. In aluminum it is a common choice for 100 A feeders and 125 A dwelling services.

Assumes NEC 2023 Table 310.16, 30 C ambient and no more than three current-carrying conductors. NM-B cable uses the 60 C column.

1 tick = 1 mm 8.25 mm
1/0 AWG Copper conductor and typical insulation, drawn to scale against a millimetre ruler.

1/0 AWG specifications

Diameter0.3249 in8.251 mm
Area105,535 cmil53.48 mm²
Copper resistance0.1195 ohm/1000 ft0.322 ohm/km
Aluminum resistance0.1968 ohm/1000 ft0.529 ohm/km
Copper weight319.4 lb/1000 ft475.4 kg/km
Nearest metric50 mm²70 mm² or larger
Solid conductor. Resistance per 1000 ft at 75 C, per km at 20 C. Stranded wire is about 2% higher.

1/0 AWG ampacity

60 C75 C90 CMax breaker
Copper125150170per table
Aluminum100120135per table
Amps. 60 C: NM-B, UF-B and most terminals on circuits of 100 A or less. 75 C: THHN/THWN with 75 C rated terminals. 90 C: for derating only.

What 1/0 gauge wire is used for

1/0 is also written 0 AWG or "one aught". It is one size larger than 1 AWG.

NEC 310.10(G) allows conductors 1/0 and larger to run in parallel, which is how very large feeders are built.

For battery and inverter cable, flexible fine-strand cable is normal and the size is set by fuse rating and voltage drop at low voltage, not by Table 310.16.

How far can you run 1/0 gauge wire?

Longest one-way run in copper that keeps voltage drop at or below 3%, single-phase.

Load120 V240 V
70 A215 ft430 ft
80 A188 ft377 ft
100 A151 ft301 ft
125 A120 ft241 ft
150 A100 ft201 ft
Resistance at 75 C. Aluminum runs are about 40% shorter.

Check a run

Voltage drop on 1/0 AWG

A
V
System
Conductor

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

1/0 gauge wire questions

How many amps can 1/0 wire carry?

Copper: 125 A at 60 C, 150 A at 75 C, 170 A at 90 C. Aluminum: 100, 120 and 135 A.

Is 1/0 the same as 0 gauge?

Yes. 1/0, 0 AWG and "one aught" are the same size, about 8.25 mm (0.325 in) in diameter for a solid conductor.

Is 1/0 aluminum good for 100 amps?

Yes. 1/0 aluminum is rated 120 A at 75 C, so it covers a 100 A feeder with some margin for voltage drop.