Gauge / 1/0 AWG / 8.25 mm
1/0 gauge wire (0 AWG)
1/0 AWG copper is rated 125 A at 60 C, 150 A at 75 C and 170 A at 90 C. Aluminum: 100 / 120 / 135 A.
1/0 AWG copper is rated 150 A at 75 C. In aluminum it is a common choice for 100 A feeders and 125 A dwelling services.
Assumes NEC 2023 Table 310.16, 30 C ambient and no more than three current-carrying conductors. NM-B cable uses the 60 C column.
1/0 AWG specifications
| Diameter | 0.3249 in | 8.251 mm |
|---|---|---|
| Area | 105,535 cmil | 53.48 mm² |
| Copper resistance | 0.1195 ohm/1000 ft | 0.322 ohm/km |
| Aluminum resistance | 0.1968 ohm/1000 ft | 0.529 ohm/km |
| Copper weight | 319.4 lb/1000 ft | 475.4 kg/km |
| Nearest metric | 50 mm² | 70 mm² or larger |
1/0 AWG ampacity
| 60 C | 75 C | 90 C | Max breaker | |
|---|---|---|---|---|
| Copper | 125 | 150 | 170 | per table |
| Aluminum | 100 | 120 | 135 | per table |
What 1/0 gauge wire is used for
- 150 A feeders in copper with 75 C terminations
- 125 A dwelling services in aluminum (NEC 310.12)
- 100 A subpanel feeders in aluminum, with room for voltage drop
- Battery and inverter cables in off-grid and marine systems
- Welding leads and car audio power runs
1/0 is also written 0 AWG or "one aught". It is one size larger than 1 AWG.
NEC 310.10(G) allows conductors 1/0 and larger to run in parallel, which is how very large feeders are built.
For battery and inverter cable, flexible fine-strand cable is normal and the size is set by fuse rating and voltage drop at low voltage, not by Table 310.16.
How far can you run 1/0 gauge wire?
Longest one-way run in copper that keeps voltage drop at or below 3%, single-phase.
| Load | 120 V | 240 V |
|---|---|---|
| 70 A | 215 ft | 430 ft |
| 80 A | 188 ft | 377 ft |
| 100 A | 151 ft | 301 ft |
| 125 A | 120 ft | 241 ft |
| 150 A | 100 ft | 201 ft |
Check a run
Voltage drop on 1/0 AWG
Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate
1/0 gauge wire questions
How many amps can 1/0 wire carry?
Copper: 125 A at 60 C, 150 A at 75 C, 170 A at 90 C. Aluminum: 100, 120 and 135 A.
Is 1/0 the same as 0 gauge?
Yes. 1/0, 0 AWG and "one aught" are the same size, about 8.25 mm (0.325 in) in diameter for a solid conductor.
Is 1/0 aluminum good for 100 amps?
Yes. 1/0 aluminum is rated 120 A at 75 C, so it covers a 100 A feeder with some margin for voltage drop.
Related sizes