Chart / NEC 2023 / 310.15 and 310.16

NEC Ampacity Chart

Table 310.16 values plus the correction and adjustment rules you need to use them, laid out for working electricians and students.

Values follow NEC 2023 Table 310.16. This is our own presentation of the values, not a reproduction of the NFPA table, notes or wording. Read the code book your jurisdiction has adopted for the governing text.

Allowable ampacity, Table 310.16

SizeCopperAluminumMax breaker
240.4(D)
60 C75 C90 C60 C75 C90 C
18 AWG --14 --- Cu 7
16 AWG --18 --- Cu 10
14 AWG 152025 --- Cu 15
12 AWG 202530 152025 Cu 20, Al 15
10 AWG 303540 253035 Cu 30, Al 25
8 AWG 405055 354045
6 AWG 556575 405055
4 AWG 708595 556575
3 AWG 85100115 657585
2 AWG 95115130 7590100
1 AWG 110130145 85100115
1/0 AWG 125150170 100120135
2/0 AWG 145175195 115135150
3/0 AWG 165200225 130155175
4/0 AWG 195230260 150180205
250 kcmil 215255290 170205230
300 kcmil 240285320 195230260
350 kcmil 260310350 210250280
400 kcmil 280335380 225270305
500 kcmil 320380430 260310350
600 kcmil 350420475 285340385
700 kcmil 385460520 315375425
750 kcmil 400475535 320385435
800 kcmil 410490555 330395445
900 kcmil 435520585 355425480
1000 kcmil 455545615 375445500
Amps at 30 C ambient, not more than three current-carrying conductors.

Ambient temperature correction, 310.15(B)

Multiply the ampacity by the factor for the ambient temperature. Factors come from the formula the NEC allows in 310.15(B): √((Tc − Ta) / (Tc − 30)).

Ambient60 C wire75 C wire90 C wire
10 C (50 F)1.291.201.15
15 C (59 F)1.221.151.12
20 C (68 F)1.151.111.08
25 C (77 F)1.081.051.04
30 C (86 F)1.001.001.00
35 C (95 F)0.910.940.96
40 C (104 F)0.820.880.91
45 C (113 F)0.710.820.87
50 C (122 F)0.580.750.82
55 C (131 F)0.410.670.76
60 C (140 F)-0.580.71
65 C (149 F)-0.470.65
70 C (158 F)-0.330.58
75 C (167 F)--0.50
80 C (176 F)--0.41
The NEC table uses 5 C bands; use the factor for the upper end of the band. A dash means the wire cannot be used at that ambient. Rooftop raceways may need an added temperature allowance.

More than three conductors, 310.15(C)(1)

Current-carrying conductorsAdjustment
4 to 680%
7 to 970%
10 to 2050%
21 to 3045%
31 to 4040%
41 and above35%
Count only current-carrying conductors. Equipment grounding conductors do not count, and a neutral that carries only unbalanced current usually does not.

Worked example

Six 10 AWG THHN copper conductors in one conduit through a 40 C attic, on 75 C terminals.

  1. Start at the 90 C column, because THHN is 90 C insulation: 40 A.
  2. Ambient correction at 40 C for 90 C wire: 0.91.
  3. Adjustment for six conductors: 80%.
  4. 40 × 0.91 × 0.80 = 29.1 A.
  5. Compare with the 75 C column (35 A) and the 240.4(D) limit (30 A). The lowest is 29.1 A.

So these conductors can serve a 25 A circuit, but not 30 A. Bump to 8 AWG for 30 A. The wire size calculator does this when you open "Ambient temperature and bundling".

NEC ampacity questions

What is NEC Table 310.16?

The main NEC table of allowable ampacities for insulated conductors rated up to 2000 V, with not more than three current-carrying conductors in a raceway, cable or earth, at 30 C ambient. Before the 2020 edition it was numbered 310.15(B)(16).

Did the ampacity values change in the 2023 NEC?

The 310.16 values used here match the 2020 and 2023 editions. The 2023 edition did change other rules, such as adding 10 A to the standard breaker sizes in 240.6(A). Check which edition your jurisdiction has adopted.

Do I apply correction and adjustment factors together?

Yes. Multiply the table value by the ambient correction factor and the adjustment factor, then compare the result with the ampacity in the terminal temperature column and use the lower of the two.