Gauge / 4 AWG / 5.19 mm
4 gauge wire
4 AWG copper is rated 70 A at 60 C, 85 A at 75 C and 95 A at 90 C. Aluminum: 55 / 65 / 75 A.
4 AWG copper is rated 70 A at 60 C and 85 A at 75 C, and it is the copper size for a 100 A dwelling service under the 83% rule.
Assumes NEC 2023 Table 310.16, 30 C ambient and no more than three current-carrying conductors. NM-B cable uses the 60 C column.
4 AWG specifications
| Diameter | 0.2043 in | 5.189 mm |
|---|---|---|
| Area | 41,741 cmil | 21.15 mm² |
| Copper resistance | 0.3022 ohm/1000 ft | 0.815 ohm/km |
| Aluminum resistance | 0.4976 ohm/1000 ft | 1.336 ohm/km |
| Copper weight | 126.3 lb/1000 ft | 188 kg/km |
| Nearest metric | 25 mm² | 25 mm² or larger |
4 AWG ampacity
| 60 C | 75 C | 90 C | Max breaker | |
|---|---|---|---|---|
| Copper | 70 | 85 | 95 | per table |
| Aluminum | 55 | 65 | 75 | per table |
What 4 gauge wire is used for
- 70 A and 80 A feeders to subpanels
- 100 A dwelling service or main feeder in copper (NEC 310.12)
- Large heat pump and electric furnace circuits per nameplate
- Generator and transfer switch feeders
NEC 310.12 lets a dwelling service or main feeder use conductors rated at 83% of the service. For 100 A, that is 83 A, which 4 AWG copper (85 A at 75 C) covers.
For a 100 A feeder that is not a dwelling main, use 3 AWG copper (100 A at 75 C) instead.
Car audio "4 gauge" amp kits use the same AWG number, but those runs are sized by fuse rating and voltage drop at 12 V, not by NEC tables.
How far can you run 4 gauge wire?
Longest one-way run in copper that keeps voltage drop at or below 3%, single-phase.
| Load | 120 V | 240 V |
|---|---|---|
| 40 A | 149 ft | 298 ft |
| 50 A | 119 ft | 238 ft |
| 60 A | 99 ft | 199 ft |
| 70 A | 85 ft | 170 ft |
| 80 A | 74 ft | 149 ft |
Check a run
Voltage drop on 4 AWG
Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate
4 gauge wire questions
How many amps can 4 gauge wire handle?
Copper: 70 A at 60 C, 85 A at 75 C, 95 A at 90 C. Aluminum: 55, 65 and 75 A.
Is 4 gauge wire good for 100 amps?
Copper 4 AWG works for a 100 A dwelling service or main feeder under the 83% rule. For any other 100 A feeder, use 3 AWG copper or 1 AWG aluminum.
What breaker for 4 gauge wire?
Up to 70 A where 60 C terminations apply, or up to 85 A with 75 C terminations. The nearest standard breakers are 70 A and 80 A.
Related sizes
4 AWG copper is the minimum for: 60 amp circuits.
Convert this size: AWG to mm². All sizes: wire gauge chart. Any size and length: voltage drop calculator.