Gauge / 4 AWG / 5.19 mm

4 gauge wire

4 AWG copper is rated 70 A at 60 C, 85 A at 75 C and 95 A at 90 C. Aluminum: 55 / 65 / 75 A.

4 AWG copper is rated 70 A at 60 C and 85 A at 75 C, and it is the copper size for a 100 A dwelling service under the 83% rule.

Assumes NEC 2023 Table 310.16, 30 C ambient and no more than three current-carrying conductors. NM-B cable uses the 60 C column.

1 tick = 1 mm 5.19 mm
4 AWG Copper conductor and typical insulation, drawn to scale against a millimetre ruler.

4 AWG specifications

Diameter0.2043 in5.189 mm
Area41,741 cmil21.15 mm²
Copper resistance0.3022 ohm/1000 ft0.815 ohm/km
Aluminum resistance0.4976 ohm/1000 ft1.336 ohm/km
Copper weight126.3 lb/1000 ft188 kg/km
Nearest metric25 mm²25 mm² or larger
Solid conductor. Resistance per 1000 ft at 75 C, per km at 20 C. Stranded wire is about 2% higher.

4 AWG ampacity

60 C75 C90 CMax breaker
Copper708595per table
Aluminum556575per table
Amps. 60 C: NM-B, UF-B and most terminals on circuits of 100 A or less. 75 C: THHN/THWN with 75 C rated terminals. 90 C: for derating only.

What 4 gauge wire is used for

NEC 310.12 lets a dwelling service or main feeder use conductors rated at 83% of the service. For 100 A, that is 83 A, which 4 AWG copper (85 A at 75 C) covers.

For a 100 A feeder that is not a dwelling main, use 3 AWG copper (100 A at 75 C) instead.

Car audio "4 gauge" amp kits use the same AWG number, but those runs are sized by fuse rating and voltage drop at 12 V, not by NEC tables.

How far can you run 4 gauge wire?

Longest one-way run in copper that keeps voltage drop at or below 3%, single-phase.

Load120 V240 V
40 A149 ft298 ft
50 A119 ft238 ft
60 A99 ft199 ft
70 A85 ft170 ft
80 A74 ft149 ft
Resistance at 75 C. Aluminum runs are about 40% shorter.

Check a run

Voltage drop on 4 AWG

A
V
System
Conductor

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

4 gauge wire questions

How many amps can 4 gauge wire handle?

Copper: 70 A at 60 C, 85 A at 75 C, 95 A at 90 C. Aluminum: 55, 65 and 75 A.

Is 4 gauge wire good for 100 amps?

Copper 4 AWG works for a 100 A dwelling service or main feeder under the 83% rule. For any other 100 A feeder, use 3 AWG copper or 1 AWG aluminum.

What breaker for 4 gauge wire?

Up to 70 A where 60 C terminations apply, or up to 85 A with 75 C terminations. The nearest standard breakers are 70 A and 80 A.

Related sizes

4 AWG copper is the minimum for: 60 amp circuits.

Convert this size: AWG to mm². All sizes: wire gauge chart. Any size and length: voltage drop calculator.