What every number on this site is based on, how we check it, and what it does not cover.
Review status
The data and formulas are cross-checked against at least two published sources and covered by automated tests. An independent review by a licensed electrician is planned; this page will name the reviewer when it is done.
Code basis: NEC 2023, US installations. Found an error? Email hello@wiregaugetool.com and we will fix it and log it below.
Wire size calculation
- Design current: the load current, times 1.25 for continuous loads (3 hours or more), per NEC 210.19(A) and 215.2(A).
- Overcurrent device: the next standard rating at or above the design current, from NEC 240.6(A). We do not apply the "next size up" allowance of 240.4(B); the conductor must carry the full breaker rating.
- Ampacity: start from Table 310.16 in the insulation's column (90 C for THHN and NM-B conductors, 60 C for UF-B). Multiply by the ambient correction factor and the adjustment factor for more than three current-carrying conductors. Cap the result at the termination column: 60 C for NM-B (334.80) and UF-B, and for THHN either your choice or the default from 110.14(C)(1): 60 C for circuits of 100 A or less and 14 to 1 AWG conductors, otherwise 75 C.
- Small conductors: 14, 12 and 10 AWG copper and 12 and 10 AWG aluminum are also held to the breaker limits of 240.4(D).
- Voltage drop: the smallest conductor whose drop at the actual load (not the 125% design current) is within your limit.
- Result: the larger of the ampacity and voltage drop sizes. We search single conductors from 18 AWG to 1000 kcmil; parallel sets are out of scope.
Formulas
- AWG diameter: d = 0.127 mm × 92(36 − n)/39, with 1/0 = 0, 2/0 = −1, 3/0 = −2, 4/0 = −3 (ASTM B258).
- Resistance: R = ρ(T) / A, with ρ(20 C) = 1.7241 × 10⁻⁸ ohm m for copper and 2.8264 × 10⁻⁸ ohm m for aluminum, and ρ(T) = ρ(20 C) × (1 + α(T − 20)), α = 0.00393 (Cu) and 0.00403 (Al). Voltage drop uses 75 C.
- Voltage drop: VD = 2 × I × R × L for single-phase and DC, √3 × I × R × L for three-phase. L is one-way length. Reactance is ignored.
- Ambient correction: √((Tc − Ta) / (Tc − 30)), as permitted by 310.15(B), rounded to two places.
- Dwelling service: conductor ampacity at 75 C of at least 83% of the service rating (310.12).
Assumptions and limits
- Copper or aluminum conductors in raceway, cable or direct burial, up to 2000 V, as covered by Table 310.16. Not free air (310.17), not overhead or other special tables.
- Solid-conductor resistance. Stranded conductors are about 2% higher; coated copper slightly higher again.
- Motor circuits, air conditioners, welders and other equipment with their own NEC articles may allow different breaker sizes. Use the nameplate and the article for that equipment.
- UK and other metric users: we convert sizes only. Current ratings under BS 7671 or IEC 60364 depend on installation method and are not published here.
- Results are for planning and estimating. They are not a substitute for a design by a qualified person or approval by the authority having jurisdiction.
How the numbers are tested
Every build runs an automated test suite before it can deploy. It checks the AWG geometry against the ASTM B258 reference table, calculated resistance against NEC Chapter 9 Table 8 (within 3%), that the ampacity table only increases with size and temperature, that aluminum never out-rates copper, the correction factors against the published table, and a set of known answers (for example 50 A on NM-B needs 6 AWG copper; 20 A at 75 C still needs 12 AWG because of 240.4(D)).
Sources
- NFPA 70, National Electrical Code, 2023 edition: Table 310.16 ampacity, 240.4(D), 240.6(A), 310.12, 310.15(B) and (C), 110.14(C). Values cited, not reproduced..
- NFPA TIA 1691 to NFPA 70 (2023), proposal reprinting Table 310.16: Cross-check of every ampacity value.
- Cerrowire ampacity charts: Second independent check of 75 C and 90 C values.
- Mike Holt, NEC 2020 Table 310.12 guide: Check of dwelling service sizes.
- ASTM B258, standard nominal diameters and areas of AWG sizes: AWG diameter formula.
- NEC Chapter 9 Table 8: Check of calculated DC resistance (within 3%).
- IEC 60228: Standard metric conductor sizes.
National Electrical Code and NEC are registered trademarks of the National Fire Protection Association. This site is not affiliated with or endorsed by the NFPA. Ampacity values are facts taken from the code and presented in our own format; read the adopted code for the governing text.
Data changelog
| Date | Change |
|---|---|
| 2026-11-29 | Corrected 8 AWG aluminum at 60 C to 35 A after cross-checking against NEC 2023 sources. |
| 2026-11-29 | Added 10 A to the standard breaker list, as in NEC 2023 240.6(A). |
| 2026-11-29 | First release: Table 310.16 values (NEC 2023), 240.4(D) limits, 310.15 correction and adjustment, 310.12 dwelling rule, AWG geometry from ASTM B258. |