Tool 02 / copper and aluminum / AC and DC
Voltage Drop Calculator
Pick a wire size, enter the current and the one-way length, and see how many volts you lose before the load.
Live
Voltage drop calculator
Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate
Voltage drop formula
VD = k × I × R × L
k is 2 for single-phase and DC (the current goes out and back), or 1.732 for balanced three-phase. I is the load current, R is the resistance of one conductor in ohms per foot, and L is the one-way length in feet. Percent drop is VD divided by the supply voltage.
Resistance comes from the conductor area and the resistivity of copper (1.724 × 10⁻⁸ ohm m at 20 C) or aluminum (2.826 × 10⁻⁸ ohm m), corrected to 75 C. Reactance is ignored, which is accurate for small conductors and slightly low for large AC feeders.
Maximum distance at 3% voltage drop
Longest one-way copper run for common circuits at full breaker load, single-phase.
| Wire | Load | 120 V | 240 V |
|---|---|---|---|
| 14 AWG | 15 A | 39 ft | 78 ft |
| 12 AWG | 20 A | 47 ft | 93 ft |
| 10 AWG | 30 A | 49 ft | 99 ft |
| 8 AWG | 40 A | 59 ft | 118 ft |
| 6 AWG | 50 A | 75 ft | 150 ft |
| 4 AWG | 70 A | 85 ft | 170 ft |
Voltage drop questions
What is an acceptable voltage drop?
The NEC informational notes recommend no more than 3% on a branch circuit and 5% total from service to the load. Sensitive electronics and motors benefit from staying under 3%. Low-voltage DC systems often target 3% for critical loads and up to 10% for lighting.
How do you calculate voltage drop?
Single-phase and DC: VD = 2 x I x R x L. Three-phase: VD = 1.732 x I x R x L. I is current in amps, R is resistance per foot of one conductor, and L is the one-way length in feet.
Does voltage drop depend on the voltage?
The volts lost depend only on current, resistance and length. The percentage drop is lower at higher voltage, which is why 240 V circuits can run twice as far as 120 V circuits for the same load and wire.
Why does this calculator use resistance at 75 C?
Conductors under load run warm. NEC Chapter 9 Table 8 lists DC resistance at 75 C, so it is the usual basis for voltage drop. Cold wire has lower resistance, so the real drop at light load will be a little less.