Gauge / 6 AWG / 4.12 mm

6 gauge wire

6 AWG copper is rated 55 A at 60 C, 65 A at 75 C and 75 A at 90 C. Aluminum: 40 / 50 / 55 A.

6 AWG copper is the usual size for 50 A circuits in NM-B and up to 65 A with 75 C terminations.

Assumes NEC 2023 Table 310.16, 30 C ambient and no more than three current-carrying conductors. NM-B cable uses the 60 C column.

1 tick = 1 mm 4.12 mm
6 AWG Copper conductor and typical insulation, drawn to scale against a millimetre ruler.

6 AWG specifications

Diameter0.162 in4.115 mm
Area26,251 cmil13.3 mm²
Copper resistance0.4805 ohm/1000 ft1.296 ohm/km
Aluminum resistance0.7912 ohm/1000 ft2.125 ohm/km
Copper weight79.5 lb/1000 ft118.3 kg/km
Nearest metric16 mm²16 mm² or larger
Solid conductor. Resistance per 1000 ft at 75 C, per km at 20 C. Stranded wire is about 2% higher.

NM-B cable: Black sheath (6/2 and 6/3 NM-B).

6 AWG ampacity

60 C75 C90 CMax breaker
Copper556575per table
Aluminum405055per table
Amps. 60 C: NM-B, UF-B and most terminals on circuits of 100 A or less. 75 C: THHN/THWN with 75 C rated terminals. 90 C: for derating only.

What 6 gauge wire is used for

In NM-B (60 C column), 6 AWG copper is rated 55 A, so it covers a 50 A breaker with room to spare.

With 75 C terminations and THHN, 6 AWG copper is rated 65 A, which is enough for a 60 A circuit.

Running a 50 A circuit 100 ft at 240 V with 6 AWG copper gives about 2% voltage drop at full load.

How far can you run 6 gauge wire?

Longest one-way run in copper that keeps voltage drop at or below 3%, single-phase.

Load120 V240 V
25 A150 ft300 ft
30 A125 ft250 ft
40 A94 ft187 ft
50 A75 ft150 ft
60 A62 ft125 ft
Resistance at 75 C. Aluminum runs are about 40% shorter.

Check a run

Voltage drop on 6 AWG

A
V
System
Conductor

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

6 gauge wire questions

How many amps can 6 gauge wire carry?

Copper: 55 A at 60 C, 65 A at 75 C, 75 A at 90 C. Aluminum: 40, 50 and 55 A.

Can 6 gauge wire handle 60 amps?

Copper with 75 C terminations, yes (65 A). In NM-B cable, no, because NM-B is held to the 60 C column (55 A).

What size wire for a 50 amp RV hookup?

6 AWG copper is the usual choice for a 50 A, 120/240 V RV pedestal. Check voltage drop on long runs.

Related sizes

6 AWG copper is the minimum for: 50 amp circuits, 60 amp circuits.

Convert this size: AWG to mm². All sizes: wire gauge chart. Any size and length: voltage drop calculator.