Gauge / 6 AWG / 4.12 mm
6 gauge wire
6 AWG copper is rated 55 A at 60 C, 65 A at 75 C and 75 A at 90 C. Aluminum: 40 / 50 / 55 A.
6 AWG copper is the usual size for 50 A circuits in NM-B and up to 65 A with 75 C terminations.
Assumes NEC 2023 Table 310.16, 30 C ambient and no more than three current-carrying conductors. NM-B cable uses the 60 C column.
6 AWG specifications
| Diameter | 0.162 in | 4.115 mm |
|---|---|---|
| Area | 26,251 cmil | 13.3 mm² |
| Copper resistance | 0.4805 ohm/1000 ft | 1.296 ohm/km |
| Aluminum resistance | 0.7912 ohm/1000 ft | 2.125 ohm/km |
| Copper weight | 79.5 lb/1000 ft | 118.3 kg/km |
| Nearest metric | 16 mm² | 16 mm² or larger |
NM-B cable: Black sheath (6/2 and 6/3 NM-B).
6 AWG ampacity
| 60 C | 75 C | 90 C | Max breaker | |
|---|---|---|---|---|
| Copper | 55 | 65 | 75 | per table |
| Aluminum | 40 | 50 | 55 | per table |
What 6 gauge wire is used for
- 50 A range circuits and NEMA 14-50 outlets
- 48 A and 40 A EV chargers (60 A and 50 A circuits)
- 50 A RV pedestals
- 60 A subpanels with THHN at 75 C
- Hot tubs and spas that call for a 50 A GFCI breaker
In NM-B (60 C column), 6 AWG copper is rated 55 A, so it covers a 50 A breaker with room to spare.
With 75 C terminations and THHN, 6 AWG copper is rated 65 A, which is enough for a 60 A circuit.
Running a 50 A circuit 100 ft at 240 V with 6 AWG copper gives about 2% voltage drop at full load.
How far can you run 6 gauge wire?
Longest one-way run in copper that keeps voltage drop at or below 3%, single-phase.
| Load | 120 V | 240 V |
|---|---|---|
| 25 A | 150 ft | 300 ft |
| 30 A | 125 ft | 250 ft |
| 40 A | 94 ft | 187 ft |
| 50 A | 75 ft | 150 ft |
| 60 A | 62 ft | 125 ft |
Check a run
Voltage drop on 6 AWG
Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate
6 gauge wire questions
How many amps can 6 gauge wire carry?
Copper: 55 A at 60 C, 65 A at 75 C, 75 A at 90 C. Aluminum: 40, 50 and 55 A.
Can 6 gauge wire handle 60 amps?
Copper with 75 C terminations, yes (65 A). In NM-B cable, no, because NM-B is held to the 60 C column (55 A).
What size wire for a 50 amp RV hookup?
6 AWG copper is the usual choice for a 50 A, 120/240 V RV pedestal. Check voltage drop on long runs.
Related sizes
6 AWG copper is the minimum for: 50 amp circuits, 60 amp circuits.
Convert this size: AWG to mm². All sizes: wire gauge chart. Any size and length: voltage drop calculator.