Circuit / 50 A breaker / NEC 2023

What size wire for 50 amps?

A 50 A circuit needs at least 6 AWG copper (or 8 AWG copper THHN when every terminal is rated 75 C), or 6 AWG aluminum at 75 C.

For a 50 A breaker, NEC 2023 Table 310.16, 30 C ambient, no more than three current-carrying conductors, runs short enough that voltage drop stays under 3%. Circuits of 100 A or less default to the 60 C column (NEC 110.14(C)).

Wire size for a 50 amp breaker

Wiring methodMaterialMinimum sizeAmpacity
NM-B cable (Romex) or 60 C terminalsCopper6 AWG55 A
THHN/THWN in conduit, 75 C terminalsCopper8 AWG50 A
60 C terminalsAluminum4 AWG55 A
75 C terminals (XHHW, SER, USE)Aluminum6 AWG50 A
Ampacity shown in the column that applies. Small conductors are also held to NEC 240.4(D) breaker limits.

Wire size for 50 amps by distance

Minimum copper size to stay at or under 3% voltage drop at a full 50 A load, single-phase. Distance is one way.

Voltage50 ft100 ft150 ft200 ft
120 V6 AWG4 AWG3 AWG1 AWG
240 V6 AWG6 AWG4 AWG4 AWG
Most circuits run below full load, so these are on the safe side. Use the calculator below for your real load and length.

How many watts on a 50 amp circuit

VoltageMaximumContinuous (80%)
120 V6,000 W4,800 W
240 V12,000 W9,600 W
Watts = volts x amps. Loads running 3 hours or more (heaters, EV charging, water heaters) are limited to 80% of the breaker: 40 A.

What runs on a 50 amp circuit

Two sizes work. 6 AWG copper works with any wiring method, including NM-B. 8 AWG copper works only as 75 C rated conductors, such as THHN in conduit, with breaker and equipment terminals rated 75 C.

If you are not sure every termination is rated 75 C, use 6 AWG copper. A 14-50 outlet in a garage also needs GFCI protection under NEC 2020 and later.

Your run

Check your 50 amp run

A
V
System
Conductor
Max voltage drop
Wire type
Hot locations and bundled wires
°C
in run

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

When to call an electrician: circuits of 50 A usually feed fixed appliances, subpanels or outdoor equipment. Most areas need a permit and inspection for new circuits, and a mistake here is a fire risk. Use these numbers to plan and price the job.

50 amp wire questions

Is 8 gauge wire OK for 50 amps?

Only as copper THHN or similar with 75 C terminations at both ends. 8/3 NM-B cable is limited to 40 A, so use 6/3 NM-B for a 50 A cable run.

What size aluminum wire for 50 amps?

6 AWG aluminum at 75 C is rated 50 A. Check that the breaker and outlet are rated for aluminum (marked AL/CU).

Other circuit sizes

Every rating on one page: wire size chart.