Circuit / 40 A breaker / NEC 2023
What size wire for 40 amps?
A 40 A circuit needs at least 8 AWG copper, or 8 AWG aluminum at 75 C.
For a 40 A breaker, NEC 2023 Table 310.16, 30 C ambient, no more than three current-carrying conductors, runs short enough that voltage drop stays under 3%. Circuits of 100 A or less default to the 60 C column (NEC 110.14(C)).
Wire size for a 40 amp breaker
| Wiring method | Material | Minimum size | Ampacity |
|---|---|---|---|
| NM-B cable (Romex) or 60 C terminals | Copper | 8 AWG | 40 A |
| THHN/THWN in conduit, 75 C terminals | Copper | 8 AWG | 50 A |
| 60 C terminals | Aluminum | 6 AWG | 40 A |
| 75 C terminals (XHHW, SER, USE) | Aluminum | 8 AWG | 40 A |
Wire size for 40 amps by distance
Minimum copper size to stay at or under 3% voltage drop at a full 40 A load, single-phase. Distance is one way.
| Voltage | 50 ft | 100 ft | 150 ft | 200 ft |
|---|---|---|---|---|
| 120 V | 8 AWG | 4 AWG | 3 AWG | 2 AWG |
| 240 V | 8 AWG | 8 AWG | 6 AWG | 4 AWG |
How many watts on a 40 amp circuit
| Voltage | Maximum | Continuous (80%) |
|---|---|---|
| 120 V | 4,800 W | 3,840 W |
| 240 V | 9,600 W | 7,680 W |
What runs on a 40 amp circuit
- Electric cooktops and smaller ranges
- Wall ovens
- 32 A EV chargers (40 A circuit)
- Heat pumps and air handlers per nameplate
8 AWG copper covers 40 A in every wiring method, including NM-B, because 8 AWG copper is rated 40 A even in the 60 C column.
Level 2 EV chargers are continuous loads. A 32 A charger needs 32 x 1.25 = 40 A of circuit capacity.
Aluminum is uncommon at this size, but 8 AWG aluminum at 75 C (40 A) works where the breaker and appliance terminals are marked AL/CU. With 60 C terminals, use 6 AWG aluminum.
Ranges and cooktops often list both a 40 A and a 50 A option in the install guide. If you might upgrade the appliance later, running 6 AWG copper now lets you swap to a 50 A breaker without pulling new wire.
Your run
Check your 40 amp run
Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate
When to call an electrician: circuits of 40 A usually feed fixed appliances, subpanels or outdoor equipment. Most areas need a permit and inspection for new circuits, and a mistake here is a fire risk. Use these numbers to plan and price the job.
40 amp wire questions
Is 10 gauge wire OK for 40 amps?
No. 10 AWG copper is limited to 30 A. Use 8 AWG copper.
What size wire for a 40 amp EV charger circuit?
8 AWG copper for a 40 A circuit, which serves a charger set to 32 A.
Other circuit sizes
Every rating on one page: wire size chart.