Circuit / 40 A breaker / NEC 2023

What size wire for 40 amps?

A 40 A circuit needs at least 8 AWG copper, or 8 AWG aluminum at 75 C.

For a 40 A breaker, NEC 2023 Table 310.16, 30 C ambient, no more than three current-carrying conductors, runs short enough that voltage drop stays under 3%. Circuits of 100 A or less default to the 60 C column (NEC 110.14(C)).

Wire size for a 40 amp breaker

Wiring methodMaterialMinimum sizeAmpacity
NM-B cable (Romex) or 60 C terminalsCopper8 AWG40 A
THHN/THWN in conduit, 75 C terminalsCopper8 AWG50 A
60 C terminalsAluminum6 AWG40 A
75 C terminals (XHHW, SER, USE)Aluminum8 AWG40 A
Ampacity shown in the column that applies. Small conductors are also held to NEC 240.4(D) breaker limits.

Wire size for 40 amps by distance

Minimum copper size to stay at or under 3% voltage drop at a full 40 A load, single-phase. Distance is one way.

Voltage50 ft100 ft150 ft200 ft
120 V8 AWG4 AWG3 AWG2 AWG
240 V8 AWG8 AWG6 AWG4 AWG
Most circuits run below full load, so these are on the safe side. Use the calculator below for your real load and length.

How many watts on a 40 amp circuit

VoltageMaximumContinuous (80%)
120 V4,800 W3,840 W
240 V9,600 W7,680 W
Watts = volts x amps. Loads running 3 hours or more (heaters, EV charging, water heaters) are limited to 80% of the breaker: 32 A.

What runs on a 40 amp circuit

8 AWG copper covers 40 A in every wiring method, including NM-B, because 8 AWG copper is rated 40 A even in the 60 C column.

Level 2 EV chargers are continuous loads. A 32 A charger needs 32 x 1.25 = 40 A of circuit capacity.

Aluminum is uncommon at this size, but 8 AWG aluminum at 75 C (40 A) works where the breaker and appliance terminals are marked AL/CU. With 60 C terminals, use 6 AWG aluminum.

Ranges and cooktops often list both a 40 A and a 50 A option in the install guide. If you might upgrade the appliance later, running 6 AWG copper now lets you swap to a 50 A breaker without pulling new wire.

Your run

Check your 40 amp run

A
V
System
Conductor
Max voltage drop
Wire type
Hot locations and bundled wires
°C
in run

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

When to call an electrician: circuits of 40 A usually feed fixed appliances, subpanels or outdoor equipment. Most areas need a permit and inspection for new circuits, and a mistake here is a fire risk. Use these numbers to plan and price the job.

40 amp wire questions

Is 10 gauge wire OK for 40 amps?

No. 10 AWG copper is limited to 30 A. Use 8 AWG copper.

What size wire for a 40 amp EV charger circuit?

8 AWG copper for a 40 A circuit, which serves a charger set to 32 A.

Other circuit sizes

Every rating on one page: wire size chart.