Circuit / 200 A breaker / NEC 2023
What size wire for 200 amps?
A 200 A circuit needs at least 3/0 AWG copper, or 250 kcmil aluminum at 75 C.
For a 200 A breaker, NEC 2023 Table 310.16, 30 C ambient, no more than three current-carrying conductors, runs short enough that voltage drop stays under 3%. Circuits over 100 A use the 75 C column.
Wire size for a 200 amp breaker
| Wiring method | Material | Minimum size | Ampacity |
|---|---|---|---|
| NM-B cable (Romex) or 60 C terminals | Copper | 250 kcmil | 215 A |
| THHN/THWN in conduit, 75 C terminals | Copper | 3/0 AWG | 200 A |
| 75 C terminals (XHHW, SER, USE) | Aluminum | 250 kcmil | 205 A |
Wire size for 200 amps by distance
Minimum copper size to stay at or under 3% voltage drop at a full 200 A load, single-phase. Distance is one way.
| Voltage | 50 ft | 100 ft | 150 ft | 200 ft |
|---|---|---|---|---|
| 120 V | 3/0 AWG | 3/0 AWG | 4/0 AWG | 300 kcmil |
| 240 V | 3/0 AWG | 3/0 AWG | 3/0 AWG | 3/0 AWG |
How many watts on a 200 amp circuit
| Voltage | Maximum | Continuous (80%) |
|---|---|---|
| 120 V | 24,000 W | 19,200 W |
| 240 V | 48,000 W | 38,400 W |
What runs on a 200 amp circuit
- Large feeders to subpanels and outbuildings
- Commercial and multi-family feeders
- Main service for most modern homes (see the 200 amp service page)
At full rating with 75 C terminations, a 200 A feeder needs 3/0 copper (200 A) or 250 kcmil aluminum (205 A).
A dwelling main service can use the 83% rule instead: 2/0 copper or 4/0 aluminum. That is why 4/0 aluminum is so common on 200 A homes.
Sizing a main service instead? See wire size for 200 amp service, where the dwelling 83% rule applies.
Your run
Check your 200 amp run
Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate
When to call an electrician: circuits of 200 A usually feed fixed appliances, subpanels or outdoor equipment. Most areas need a permit and inspection for new circuits, and a mistake here is a fire risk. Use these numbers to plan and price the job.
200 amp wire questions
Is 4/0 aluminum good for 200 amps?
For a dwelling main service or main feeder, yes, under NEC 310.12. For any other 200 A feeder, 4/0 aluminum (180 A at 75 C) is too small; use 250 kcmil aluminum.
What size ground wire for 200 amps?
The equipment grounding conductor for a 200 A feeder is 6 AWG copper or 4 AWG aluminum (NEC Table 250.122). A grounding electrode conductor is sized differently, from Table 250.66.
Other circuit sizes
Every rating on one page: wire size chart.