Circuit / 200 A breaker / NEC 2023

What size wire for 200 amps?

A 200 A circuit needs at least 3/0 AWG copper, or 250 kcmil aluminum at 75 C.

For a 200 A breaker, NEC 2023 Table 310.16, 30 C ambient, no more than three current-carrying conductors, runs short enough that voltage drop stays under 3%. Circuits over 100 A use the 75 C column.

Wire size for a 200 amp breaker

Wiring methodMaterialMinimum sizeAmpacity
NM-B cable (Romex) or 60 C terminalsCopper250 kcmil215 A
THHN/THWN in conduit, 75 C terminalsCopper3/0 AWG200 A
75 C terminals (XHHW, SER, USE)Aluminum250 kcmil205 A
Ampacity shown in the column that applies. Small conductors are also held to NEC 240.4(D) breaker limits.

Wire size for 200 amps by distance

Minimum copper size to stay at or under 3% voltage drop at a full 200 A load, single-phase. Distance is one way.

Voltage50 ft100 ft150 ft200 ft
120 V3/0 AWG3/0 AWG4/0 AWG300 kcmil
240 V3/0 AWG3/0 AWG3/0 AWG3/0 AWG
Most circuits run below full load, so these are on the safe side. Use the calculator below for your real load and length.

How many watts on a 200 amp circuit

VoltageMaximumContinuous (80%)
120 V24,000 W19,200 W
240 V48,000 W38,400 W
Watts = volts x amps. Loads running 3 hours or more (heaters, EV charging, water heaters) are limited to 80% of the breaker: 160 A.

What runs on a 200 amp circuit

At full rating with 75 C terminations, a 200 A feeder needs 3/0 copper (200 A) or 250 kcmil aluminum (205 A).

A dwelling main service can use the 83% rule instead: 2/0 copper or 4/0 aluminum. That is why 4/0 aluminum is so common on 200 A homes.

Sizing a main service instead? See wire size for 200 amp service, where the dwelling 83% rule applies.

Your run

Check your 200 amp run

A
V
System
Conductor
Max voltage drop
Wire type
Terminals rated
Hot locations and bundled wires
°C
in run

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

When to call an electrician: circuits of 200 A usually feed fixed appliances, subpanels or outdoor equipment. Most areas need a permit and inspection for new circuits, and a mistake here is a fire risk. Use these numbers to plan and price the job.

200 amp wire questions

Is 4/0 aluminum good for 200 amps?

For a dwelling main service or main feeder, yes, under NEC 310.12. For any other 200 A feeder, 4/0 aluminum (180 A at 75 C) is too small; use 250 kcmil aluminum.

What size ground wire for 200 amps?

The equipment grounding conductor for a 200 A feeder is 6 AWG copper or 4 AWG aluminum (NEC Table 250.122). A grounding electrode conductor is sized differently, from Table 250.66.

Other circuit sizes

Every rating on one page: wire size chart.