Service / 200 A / NEC 310.12
Wire size for 200 amp service
For a 200 A home service, use at least 2/0 AWG copper or 4/0 AWG aluminum. Where the full 200 A rating is needed, use 3/0 AWG copper or 250 kcmil aluminum.
200 A is the standard service size for new single-family homes in the US, and the wire size depends on whether the dwelling 83% rule applies.
NEC 2023 310.12 and Table 310.16, 75 C column, 30 C ambient.
200 amp service wire sizes
| Use | Rule | Copper | Aluminum |
|---|---|---|---|
| Dwelling service or main feeder | 83% of 200 A = 166 A | 2/0 AWG (175 A) | 4/0 AWG (180 A) |
| Subpanel feeder, non-dwelling service | Full 200 A | 3/0 AWG (200 A) | 250 kcmil (205 A) |
How the 83% rule works
NEC 310.12 covers one-family dwellings and the individual units of two-family and multifamily dwellings. The service-entrance conductors, or the main feeder that carries the whole load of the unit, may have an ampacity of 83% of the service rating. For 200 A that is 166 A, and the smallest conductors that reach it in the 75 C column are 2/0 AWG copper and 4/0 AWG aluminum.
The rule reflects how homes draw power: the whole-house load almost never sits at the service rating for long. It does not change the service size itself, which still comes from a load calculation under NEC Article 220.
4/0 aluminum is the most common choice for 200 A residential services and main feeders: it costs far less than 2/0 copper and is easier to buy as SER or URD cable.
The 83% rule only applies to the service or main feeder that carries the whole load of a dwelling unit. A 200 A feeder to a subpanel, a 200 A service on a commercial building, or a feeder serving part of a home gets full-rated wire.
The utility usually owns the service drop or lateral up to the meter. Your sizing job starts at the service-entrance conductors from the meter to the main disconnect.
Grounding electrode conductor for 2/0 copper or 4/0 aluminum service conductors: 4 AWG copper or 2 AWG aluminum (NEC Table 250.66). Ground rods need no larger than 6 AWG copper.
Service work is for a licensed electrician. It needs a permit, an inspection and coordination with your utility, and it cannot be turned off at your own panel. Use this page to check a quote or plan an upgrade.
200 amp service questions
Is 4/0 aluminum enough for 200 amp service?
Yes, for a dwelling service or main feeder under NEC 310.12, because it needs only 83% of 200 A (166 A) and 4/0 aluminum is rated 180 A at 75 C.
What size copper wire for 200 amp service?
2/0 copper for a dwelling under the 83% rule. 3/0 copper where the full 200 A rating is needed.
What size wire from a 200 amp main panel to a 100 amp subpanel?
Size the feeder for 100 A at full rating: 3 AWG copper or 1 AWG aluminum at 75 C. The 83% rule does not apply to subpanel feeders.