Service / 200 A / NEC 310.12

Wire size for 200 amp service

For a 200 A home service, use at least 2/0 AWG copper or 4/0 AWG aluminum. Where the full 200 A rating is needed, use 3/0 AWG copper or 250 kcmil aluminum.

200 A is the standard service size for new single-family homes in the US, and the wire size depends on whether the dwelling 83% rule applies.

NEC 2023 310.12 and Table 310.16, 75 C column, 30 C ambient.

200 amp service wire sizes

UseRuleCopperAluminum
Dwelling service or main feeder83% of 200 A = 166 A2/0 AWG (175 A)4/0 AWG (180 A)
Subpanel feeder, non-dwelling serviceFull 200 A3/0 AWG (200 A)250 kcmil (205 A)
Ampacity in brackets, 75 C column. Correct for ambient temperature and conductor count where they apply.

How the 83% rule works

NEC 310.12 covers one-family dwellings and the individual units of two-family and multifamily dwellings. The service-entrance conductors, or the main feeder that carries the whole load of the unit, may have an ampacity of 83% of the service rating. For 200 A that is 166 A, and the smallest conductors that reach it in the 75 C column are 2/0 AWG copper and 4/0 AWG aluminum.

The rule reflects how homes draw power: the whole-house load almost never sits at the service rating for long. It does not change the service size itself, which still comes from a load calculation under NEC Article 220.

4/0 aluminum is the most common choice for 200 A residential services and main feeders: it costs far less than 2/0 copper and is easier to buy as SER or URD cable.

The 83% rule only applies to the service or main feeder that carries the whole load of a dwelling unit. A 200 A feeder to a subpanel, a 200 A service on a commercial building, or a feeder serving part of a home gets full-rated wire.

The utility usually owns the service drop or lateral up to the meter. Your sizing job starts at the service-entrance conductors from the meter to the main disconnect.

Grounding electrode conductor for 2/0 copper or 4/0 aluminum service conductors: 4 AWG copper or 2 AWG aluminum (NEC Table 250.66). Ground rods need no larger than 6 AWG copper.

Service work is for a licensed electrician. It needs a permit, an inspection and coordination with your utility, and it cannot be turned off at your own panel. Use this page to check a quote or plan an upgrade.

200 amp service questions

Is 4/0 aluminum enough for 200 amp service?

Yes, for a dwelling service or main feeder under NEC 310.12, because it needs only 83% of 200 A (166 A) and 4/0 aluminum is rated 180 A at 75 C.

What size copper wire for 200 amp service?

2/0 copper for a dwelling under the 83% rule. 3/0 copper where the full 200 A rating is needed.

What size wire from a 200 amp main panel to a 100 amp subpanel?

Size the feeder for 100 A at full rating: 3 AWG copper or 1 AWG aluminum at 75 C. The 83% rule does not apply to subpanel feeders.