Circuit / 100 A breaker / NEC 2023

What size wire for 100 amps?

A 100 A circuit needs at least 1 AWG copper (or 3 AWG copper THHN when every terminal is rated 75 C), or 1 AWG aluminum at 75 C.

For a 100 A breaker, NEC 2023 Table 310.16, 30 C ambient, no more than three current-carrying conductors, runs short enough that voltage drop stays under 3%. Circuits of 100 A or less default to the 60 C column (NEC 110.14(C)).

Wire size for a 100 amp breaker

Wiring methodMaterialMinimum sizeAmpacity
NM-B cable (Romex) or 60 C terminalsCopper1 AWG110 A
THHN/THWN in conduit, 75 C terminalsCopper3 AWG100 A
60 C terminalsAluminum1/0 AWG100 A
75 C terminals (XHHW, SER, USE)Aluminum1 AWG100 A
Ampacity shown in the column that applies. Small conductors are also held to NEC 240.4(D) breaker limits.

Wire size for 100 amps by distance

Minimum copper size to stay at or under 3% voltage drop at a full 100 A load, single-phase. Distance is one way.

Voltage50 ft100 ft150 ft200 ft
120 V1 AWG1 AWG1/0 AWG3/0 AWG
240 V1 AWG1 AWG1 AWG1 AWG
Most circuits run below full load, so these are on the safe side. Use the calculator below for your real load and length.

How many watts on a 100 amp circuit

VoltageMaximumContinuous (80%)
120 V12,000 W9,600 W
240 V24,000 W19,200 W
Watts = volts x amps. Loads running 3 hours or more (heaters, EV charging, water heaters) are limited to 80% of the breaker: 80 A.

What runs on a 100 amp circuit

For a general 100 A feeder at 75 C, the answer is 3 AWG copper or 1 AWG aluminum.

If the 100 A conductors are the main service or main feeder for a dwelling, NEC 310.12 lets you size at 83%, so 4 AWG copper or 2 AWG aluminum is enough. See the 100 amp service page.

Most 100 A subpanel feeders are run in aluminum (1 AWG or larger) because the cost difference is large at this size.

Sizing a main service instead? See wire size for 100 amp service, where the dwelling 83% rule applies.

Your run

Check your 100 amp run

A
V
System
Conductor
Max voltage drop
Wire type
Terminals rated
Hot locations and bundled wires
°C
in run

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

When to call an electrician: circuits of 100 A usually feed fixed appliances, subpanels or outdoor equipment. Most areas need a permit and inspection for new circuits, and a mistake here is a fire risk. Use these numbers to plan and price the job.

100 amp wire questions

Is 2 gauge aluminum OK for 100 amps?

Only for a dwelling main service or main feeder under NEC 310.12. For a subpanel feeder at full rating, 2 AWG aluminum (90 A at 75 C) is too small; use 1 AWG aluminum.

What size ground wire for a 100 amp subpanel?

The equipment grounding conductor for a 100 A circuit is 8 AWG copper or 6 AWG aluminum (NEC Table 250.122).

Other circuit sizes

Every rating on one page: wire size chart.