Circuit / 60 A breaker / NEC 2023

What size wire for 60 amps?

A 60 A circuit needs at least 4 AWG copper (or 6 AWG copper THHN when every terminal is rated 75 C), or 4 AWG aluminum at 75 C.

For a 60 A breaker, NEC 2023 Table 310.16, 30 C ambient, no more than three current-carrying conductors, runs short enough that voltage drop stays under 3%. Circuits of 100 A or less default to the 60 C column (NEC 110.14(C)).

Wire size for a 60 amp breaker

Wiring methodMaterialMinimum sizeAmpacity
NM-B cable (Romex) or 60 C terminalsCopper4 AWG70 A
THHN/THWN in conduit, 75 C terminalsCopper6 AWG65 A
60 C terminalsAluminum3 AWG65 A
75 C terminals (XHHW, SER, USE)Aluminum4 AWG65 A
Ampacity shown in the column that applies. Small conductors are also held to NEC 240.4(D) breaker limits.

Wire size for 60 amps by distance

Minimum copper size to stay at or under 3% voltage drop at a full 60 A load, single-phase. Distance is one way.

Voltage50 ft100 ft150 ft200 ft
120 V4 AWG3 AWG2 AWG1/0 AWG
240 V4 AWG4 AWG4 AWG3 AWG
Most circuits run below full load, so these are on the safe side. Use the calculator below for your real load and length.

How many watts on a 60 amp circuit

VoltageMaximumContinuous (80%)
120 V7,200 W5,760 W
240 V14,400 W11,520 W
Watts = volts x amps. Loads running 3 hours or more (heaters, EV charging, water heaters) are limited to 80% of the breaker: 48 A.

What runs on a 60 amp circuit

With 75 C terminations, 6 AWG copper (65 A) covers a 60 A circuit. In NM-B, or wherever 60 C applies, step up to 4 AWG copper (70 A).

For aluminum feeders to a 60 A subpanel, 4 AWG aluminum at 75 C (65 A) is the usual choice.

Your run

Check your 60 amp run

A
V
System
Conductor
Max voltage drop
Wire type
Hot locations and bundled wires
°C
in run

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

When to call an electrician: circuits of 60 A usually feed fixed appliances, subpanels or outdoor equipment. Most areas need a permit and inspection for new circuits, and a mistake here is a fire risk. Use these numbers to plan and price the job.

60 amp wire questions

Can I use 6 gauge wire for 60 amps?

Copper 6 AWG with 75 C terminations, yes (65 A). In NM-B cable it is only rated 55 A, so use 4 AWG.

What size wire for a 60 amp subpanel 100 feet away?

At 240 V and a full 60 A, 6 AWG copper gives about 2.4% drop at 100 ft. Most designs use 4 AWG aluminum or 6 AWG copper. Run the calculator with your real load.