Circuit / 30 A breaker / NEC 2023

What size wire for 30 amps?

A 30 A circuit needs at least 10 AWG copper, or 8 AWG aluminum at 75 C.

For a 30 A breaker, NEC 2023 Table 310.16, 30 C ambient, no more than three current-carrying conductors, runs short enough that voltage drop stays under 3%. Circuits of 100 A or less default to the 60 C column (NEC 110.14(C)).

Wire size for a 30 amp breaker

Wiring methodMaterialMinimum sizeAmpacity
NM-B cable (Romex) or 60 C terminalsCopper10 AWG30 A
THHN/THWN in conduit, 75 C terminalsCopper10 AWG35 A
60 C terminalsAluminum8 AWG35 A
75 C terminals (XHHW, SER, USE)Aluminum8 AWG40 A
Ampacity shown in the column that applies. Small conductors are also held to NEC 240.4(D) breaker limits.

Wire size for 30 amps by distance

Minimum copper size to stay at or under 3% voltage drop at a full 30 A load, single-phase. Distance is one way.

Voltage50 ft100 ft150 ft200 ft
120 V8 AWG6 AWG4 AWG3 AWG
240 V10 AWG8 AWG8 AWG6 AWG
Most circuits run below full load, so these are on the safe side. Use the calculator below for your real load and length.

How many watts on a 30 amp circuit

VoltageMaximumContinuous (80%)
120 V3,600 W2,880 W
240 V7,200 W5,760 W
Watts = volts x amps. Loads running 3 hours or more (heaters, EV charging, water heaters) are limited to 80% of the breaker: 24 A.

What runs on a 30 amp circuit

10 AWG copper is the answer for nearly every 30 A circuit, whether NM-B or THHN, because 240.4(D) caps 10 AWG at 30 A.

Water heaters count as continuous loads. A 4,500 W, 240 V heater draws 18.75 A, and 125% of that is 23.4 A, which fits a 30 A circuit.

Your run

Check your 30 amp run

A
V
System
Conductor
Max voltage drop
Wire type
Hot locations and bundled wires
°C
in run

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

When to call an electrician: circuits of 30 A usually feed fixed appliances, subpanels or outdoor equipment. Most areas need a permit and inspection for new circuits, and a mistake here is a fire risk. Use these numbers to plan and price the job.

30 amp wire questions

Can I use 12 gauge wire on a 30 amp breaker?

No. 12 AWG copper is limited to a 20 A breaker. A 30 A breaker needs 10 AWG copper.

What size wire for a 30 amp RV plug?

10 AWG copper for a TT-30 (120 V, 30 A). At a full 30 A, 10 AWG passes 3% voltage drop at about 50 ft, so longer runs usually go up to 8 AWG or 6 AWG.

Other circuit sizes

Every rating on one page: wire size chart.