Gauge / 8 AWG / 3.26 mm

8 gauge wire

8 AWG copper is rated 40 A at 60 C, 50 A at 75 C and 55 A at 90 C. Aluminum: 35 / 40 / 45 A.

8 AWG copper carries 40 A in NM-B cable and 50 A as individual THHN conductors with 75 C terminations.

Assumes NEC 2023 Table 310.16, 30 C ambient and no more than three current-carrying conductors. NM-B cable uses the 60 C column.

1 tick = 1 mm 3.26 mm
8 AWG Copper conductor and typical insulation, drawn to scale against a millimetre ruler.

8 AWG specifications

Diameter0.1285 in3.264 mm
Area16,510 cmil8.37 mm²
Copper resistance0.764 ohm/1000 ft2.061 ohm/km
Aluminum resistance1.2581 ohm/1000 ft3.379 ohm/km
Copper weight50 lb/1000 ft74.4 kg/km
Nearest metric10 mm²10 mm² or larger
Solid conductor. Resistance per 1000 ft at 75 C, per km at 20 C. Stranded wire is about 2% higher.

NM-B cable: Black sheath (8/2 and 8/3 NM-B).

8 AWG ampacity

60 C75 C90 CMax breaker
Copper405055per table
Aluminum354045per table
Amps. 60 C: NM-B, UF-B and most terminals on circuits of 100 A or less. 75 C: THHN/THWN with 75 C rated terminals. 90 C: for derating only.

What 8 gauge wire is used for

NM-B cable is limited to the 60 C column (NEC 334.80), so 8/3 NM-B is a 40 A cable. The same copper as THHN in conduit with 75 C terminations is rated 50 A.

An EV charger set to 32 A is a continuous load: 32 x 1.25 = 40 A, which is why 32 A chargers usually sit on a 40 A breaker with 8 AWG copper.

8 AWG aluminum is rated 40 A at 75 C, the same as 8 AWG copper in the 60 C column.

How far can you run 8 gauge wire?

Longest one-way run in copper that keeps voltage drop at or below 3%, single-phase.

Load120 V240 V
20 A118 ft236 ft
25 A94 ft188 ft
30 A79 ft157 ft
40 A59 ft118 ft
50 A47 ft94 ft
Resistance at 75 C. Aluminum runs are about 40% shorter.

Check a run

Voltage drop on 8 AWG

A
V
System
Conductor

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

8 gauge wire questions

How many amps can 8 gauge wire carry?

Copper: 40 A at 60 C (NM-B), 50 A at 75 C, 55 A at 90 C. Aluminum: 35, 40 and 45 A.

Can I use 8 gauge wire for a 50 amp breaker?

Only as copper conductors rated 75 C or higher with breaker and equipment terminals rated 75 C, typically THHN in conduit. 8/3 NM-B cable is limited to 40 A.

Is 8 gauge wire big enough for a stove?

For a range or cooktop that calls for a 40 A circuit, yes. Many full-size ranges call for 50 A, which needs 6 AWG in NM-B.

Related sizes

8 AWG copper is the minimum for: 50 amp circuits, 40 amp circuits.

Convert this size: AWG to mm². All sizes: wire gauge chart. Any size and length: voltage drop calculator.