Gauge / 12 AWG / 2.05 mm

12 gauge wire

12 AWG copper is rated 20 A at 60 C, 25 A at 75 C and 30 A at 90 C. The breaker is limited to 20 A by NEC 240.4(D). Aluminum: 15 / 20 / 25 A, 15 A breaker max.

12 AWG copper is the standard wire for a 20 A circuit and the size most electricians use for kitchen, bathroom and laundry outlets.

Assumes NEC 2023 Table 310.16, 30 C ambient and no more than three current-carrying conductors. NM-B cable uses the 60 C column.

1 tick = 1 mm 2.05 mm
12 AWG Copper conductor and typical insulation, drawn to scale against a millimetre ruler.

12 AWG specifications

Diameter0.0808 in2.053 mm
Area6,530 cmil3.31 mm²
Copper resistance1.9315 ohm/1000 ft5.211 ohm/km
Aluminum resistance3.1807 ohm/1000 ft8.542 ohm/km
Copper weight19.8 lb/1000 ft29.4 kg/km
Nearest metric4 mm²4 mm² or larger
Solid conductor. Resistance per 1000 ft at 75 C, per km at 20 C. Stranded wire is about 2% higher.

NM-B cable: Yellow sheath (12/2 and 12/3 NM-B).

12 AWG ampacity

60 C75 C90 CMax breaker
Copper20253020
Aluminum15202515
Amps. 60 C: NM-B, UF-B and most terminals on circuits of 100 A or less. 75 C: THHN/THWN with 75 C rated terminals. 90 C: for derating only.

What 12 gauge wire is used for

NEC 240.4(D) caps 12 AWG copper at a 20 A breaker even though the 75 C and 90 C columns list 25 A and 30 A.

12 AWG aluminum is listed in Table 310.16 but is limited to 15 A by 240.4(D) and is rarely used for branch circuits today.

At 20 A on 120 V, 12 AWG reaches 3% voltage drop at about 47 ft one way. For a 100 ft run at full load, step up to 10 AWG or larger.

How far can you run 12 gauge wire?

Longest one-way run in copper that keeps voltage drop at or below 3%, single-phase.

Load120 V240 V
5 A186 ft373 ft
10 A93 ft186 ft
15 A62 ft124 ft
20 A47 ft93 ft
Resistance at 75 C. Aluminum runs are about 40% shorter.

Check a run

Voltage drop on 12 AWG

A
V
System
Conductor

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

12 gauge wire questions

How many amps can 12 gauge wire carry?

20 A on a standard branch circuit. That is the breaker limit set by NEC 240.4(D) for 12 AWG copper.

Can I use 12 gauge wire on a 15 amp circuit?

Yes. Larger wire on a smaller breaker is always allowed, and it reduces voltage drop on long runs.

Can 12 gauge wire go on a 30 amp breaker?

No. A 30 A breaker needs at least 10 AWG copper.

Related sizes

Convert this size: AWG to mm². All sizes: wire gauge chart. Any size and length: voltage drop calculator. Cords: extension cord gauge chart. Audio: speaker wire gauge chart.