Gauge / 12 AWG / 2.05 mm
12 gauge wire
12 AWG copper is rated 20 A at 60 C, 25 A at 75 C and 30 A at 90 C. The breaker is limited to 20 A by NEC 240.4(D). Aluminum: 15 / 20 / 25 A, 15 A breaker max.
12 AWG copper is the standard wire for a 20 A circuit and the size most electricians use for kitchen, bathroom and laundry outlets.
Assumes NEC 2023 Table 310.16, 30 C ambient and no more than three current-carrying conductors. NM-B cable uses the 60 C column.
12 AWG specifications
| Diameter | 0.0808 in | 2.053 mm |
|---|---|---|
| Area | 6,530 cmil | 3.31 mm² |
| Copper resistance | 1.9315 ohm/1000 ft | 5.211 ohm/km |
| Aluminum resistance | 3.1807 ohm/1000 ft | 8.542 ohm/km |
| Copper weight | 19.8 lb/1000 ft | 29.4 kg/km |
| Nearest metric | 4 mm² | 4 mm² or larger |
NM-B cable: Yellow sheath (12/2 and 12/3 NM-B).
12 AWG ampacity
| 60 C | 75 C | 90 C | Max breaker | |
|---|---|---|---|---|
| Copper | 20 | 25 | 30 | 20 |
| Aluminum | 15 | 20 | 25 | 15 |
What 12 gauge wire is used for
- 20 A kitchen countertop small-appliance circuits
- 20 A bathroom and laundry receptacle circuits
- Garage and workshop receptacles
- Dedicated circuits for dishwashers, disposals and microwaves rated for 20 A
- Long 15 A runs where 14 AWG would drop too much voltage
NEC 240.4(D) caps 12 AWG copper at a 20 A breaker even though the 75 C and 90 C columns list 25 A and 30 A.
12 AWG aluminum is listed in Table 310.16 but is limited to 15 A by 240.4(D) and is rarely used for branch circuits today.
At 20 A on 120 V, 12 AWG reaches 3% voltage drop at about 47 ft one way. For a 100 ft run at full load, step up to 10 AWG or larger.
How far can you run 12 gauge wire?
Longest one-way run in copper that keeps voltage drop at or below 3%, single-phase.
| Load | 120 V | 240 V |
|---|---|---|
| 5 A | 186 ft | 373 ft |
| 10 A | 93 ft | 186 ft |
| 15 A | 62 ft | 124 ft |
| 20 A | 47 ft | 93 ft |
Check a run
Voltage drop on 12 AWG
Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate
12 gauge wire questions
How many amps can 12 gauge wire carry?
20 A on a standard branch circuit. That is the breaker limit set by NEC 240.4(D) for 12 AWG copper.
Can I use 12 gauge wire on a 15 amp circuit?
Yes. Larger wire on a smaller breaker is always allowed, and it reduces voltage drop on long runs.
Can 12 gauge wire go on a 30 amp breaker?
No. A 30 A breaker needs at least 10 AWG copper.
Related sizes