Tool / NEC 2023 Chapter 9
Conduit fill calculator
Pick the raceway, add your wires, and get the smallest trade size that meets NEC fill limits. Charts for EMT and PVC Schedule 40 are below.
Conduit fill calculator
Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate
EMT conduit fill chart
Maximum number of THHN/THWN-2 conductors of one size, at 40% fill.
| Wire | 1/2 in | 3/4 in | 1 in | 1-1/4 in | 1-1/2 in | 2 in | 2-1/2 in | 3 in |
|---|---|---|---|---|---|---|---|---|
| 14 AWG | 12 | 22 | 35 | 61 | 84 | 138 | 241 | 364 |
| 12 AWG | 9 | 16 | 26 | 45 | 61 | 101 | 176 | 266 |
| 10 AWG | 5 | 10 | 16 | 28 | 38 | 63 | 111 | 167 |
| 8 AWG | 3 | 6 | 9 | 16 | 22 | 36 | 64 | 96 |
| 6 AWG | 1 | 4 | 7 | 12 | 16 | 26 | 46 | 69 |
| 4 AWG | 1 | 2 | 4 | 7 | 10 | 16 | 28 | 43 |
| 3 AWG | 1 | 1 | 3 | 6 | 8 | 13 | 24 | 36 |
| 2 AWG | 1 | 1 | 3 | 5 | 7 | 11 | 20 | 30 |
| 1 AWG | 1 | 1 | 1 | 4 | 5 | 8 | 15 | 22 |
| 1/0 AWG | 0 | 1 | 1 | 3 | 4 | 7 | 12 | 19 |
| 2/0 AWG | 0 | 1 | 1 | 2 | 3 | 6 | 10 | 16 |
| 3/0 AWG | 0 | 1 | 1 | 1 | 3 | 5 | 8 | 13 |
| 4/0 AWG | 0 | 0 | 1 | 1 | 1 | 4 | 7 | 11 |
PVC Schedule 40 / HDPE conduit fill chart
Maximum number of THHN/THWN-2 conductors of one size, at 40% fill.
| Wire | 1/2 in | 3/4 in | 1 in | 1-1/4 in | 1-1/2 in | 2 in | 2-1/2 in | 3 in |
|---|---|---|---|---|---|---|---|---|
| 14 AWG | 11 | 21 | 34 | 60 | 82 | 135 | 193 | 299 |
| 12 AWG | 8 | 15 | 25 | 43 | 59 | 99 | 141 | 218 |
| 10 AWG | 5 | 9 | 15 | 27 | 37 | 62 | 89 | 137 |
| 8 AWG | 3 | 5 | 9 | 16 | 21 | 36 | 51 | 79 |
| 6 AWG | 1 | 4 | 6 | 11 | 15 | 26 | 37 | 57 |
| 4 AWG | 1 | 1 | 4 | 7 | 9 | 16 | 22 | 35 |
| 3 AWG | 1 | 1 | 3 | 6 | 8 | 13 | 19 | 30 |
| 2 AWG | 1 | 1 | 3 | 5 | 7 | 11 | 16 | 25 |
| 1 AWG | 0 | 1 | 1 | 3 | 5 | 8 | 12 | 18 |
| 1/0 AWG | 0 | 1 | 1 | 3 | 4 | 7 | 10 | 15 |
| 2/0 AWG | 0 | 1 | 1 | 2 | 3 | 6 | 8 | 13 |
| 3/0 AWG | 0 | 1 | 1 | 1 | 3 | 5 | 7 | 11 |
| 4/0 AWG | 0 | 0 | 1 | 1 | 1 | 4 | 6 | 9 |
How conduit fill is calculated
- Add up the wire area: each conductor's area comes from Chapter 9 Table 5 for its insulation type and size. THHN is smaller than THW or XHHW of the same gauge.
- Pick the fill limit: 53% for one conductor, 31% for two, 40% for three or more (Chapter 9 Table 1).
- Compare with the raceway: the internal area of each trade size comes from Chapter 9 Table 4. Different raceway types of the same trade size have different areas, so 1 in PVC Schedule 80 holds less than 1 in EMT.
- Choose the smallest trade size whose allowed area covers the total.
Fill is the minimum. Long pulls with several bends often need a size up to keep pulling tension and sidewall pressure down. For ampacity with more than three current-carrying conductors, use the wire size calculator or the NEC ampacity chart.
Conduit fill questions
How many 12 gauge wires can go in 1/2 inch EMT?
9 THHN conductors, using NEC Chapter 9 at 40% fill. Count the equipment ground if it is insulated.
What is the 40% conduit fill rule?
NEC Chapter 9 Table 1 limits conductors to 40% of the raceway cross-section when there are three or more. One conductor may fill 53% and two conductors 31%, because two round wires jam more easily in a pull.
Do ground wires count in conduit fill?
Yes. Equipment grounding and bonding conductors count toward fill (Chapter 9 Note 3). Use the actual area: bare conductors from Table 8, insulated ones from Table 5.
Does conduit fill change the wire ampacity?
Fill and ampacity are separate checks. More than three current-carrying conductors in one raceway also requires the adjustment factors of NEC 310.15(C)(1), which reduce ampacity. The wire size calculator applies them under "Hot locations and bundled wires".
What about nipples?
A raceway 24 inches or shorter between boxes or enclosures may be filled to 60% (Chapter 9 Note 4), and the bundling derate does not apply there.