Guide / conductors
Copper vs aluminum wire
Aluminum carries about 61% of the current of copper the same size, so it is usually two sizes larger for the same job. Use copper for branch circuits; aluminum is standard for feeders and services, where it saves a lot of money.
Sizes below from NEC 2023 Table 310.16 at 75 C, full rating.
Copper and aluminum sizes for the same breaker
| Breaker | Copper, 75 C | Aluminum, 75 C |
|---|---|---|
| 30 A | 10 AWG | 8 AWG |
| 60 A | 6 AWG | 4 AWG |
| 100 A | 3 AWG | 1 AWG |
| 125 A | 1 AWG | 2/0 AWG |
| 150 A | 1/0 AWG | 3/0 AWG |
| 200 A | 3/0 AWG | 250 kcmil |
| 400 A | 600 kcmil | 900 kcmil |
Side by side
| Copper | Aluminum | |
|---|---|---|
| Conductivity | 100% | About 61% |
| Size for same amps | Base size | Usually 2 AWG sizes larger |
| Weight | Heavy | About half the weight for the same ampacity |
| Cost | Higher | Much lower at feeder and service sizes |
| Terminations | Any rated terminal | Only terminals marked AL/CU or AL |
| Typical use today | Branch circuits, 14 to 6 AWG | Feeders, services, SER and URD cable |
The old aluminum wiring problem
From roughly the mid-1960s to the mid-1970s, some US homes were wired with solid aluminum branch circuits on devices made for copper. Aluminum expands and creeps more than copper, and its oxide layer resists current, so those connections loosened and overheated. That history is why many people distrust aluminum.
Modern aluminum building wire uses AA-8000 series alloy, which the NEC requires for the common building wire types in 8 AWG and larger, and it is installed mainly at feeder and service sizes with lugs designed for it. If you own a home with old solid aluminum branch circuits, have an electrician assess it; repairs use listed connectors made for the purpose.
Terminating aluminum correctly
- Use lugs and breakers marked AL/CU (or CO/ALR for small devices).
- Wire-brush the conductor and apply antioxidant compound where the lug maker calls for it.
- Torque to the value on the equipment label with a torque tool (NEC 110.14(D)).
- Never join copper and aluminum in a standard twist-on connector.
Sizing a feeder? The wire size calculator handles both materials, and the wire size chart lists both for every breaker.
Copper and aluminum questions
Is aluminum wire safe?
Modern aluminum building wire (AA-8000 series alloy) used for feeders and services is safe when installed with AL/CU-rated lugs at the correct torque. The fire problems came from 1960s and 1970s solid aluminum branch-circuit wiring on devices not designed for it.
How much bigger does aluminum wire need to be?
Usually two AWG sizes larger for the same ampacity, because aluminum has about 61% of copper's conductivity. For example, a 100 A feeder at 75 C needs 3 AWG copper or 1 AWG aluminum.
Can I connect copper and aluminum together?
Only with a connector listed for both metals (marked AL/CU, or a purpose-made splice such as a listed copper-aluminum crimp or connector). Never twist them together in a standard wire nut.
Why is aluminum used for services?
Cost and weight. At service sizes, aluminum costs far less than copper for the same ampacity and weighs about half as much, which matters on long runs and overhead drops.