Gauge / 2/0 AWG / 9.27 mm
2/0 gauge wire (00 AWG)
2/0 AWG copper is rated 145 A at 60 C, 175 A at 75 C and 195 A at 90 C. Aluminum: 115 / 135 / 150 A.
2/0 AWG copper is rated 175 A at 75 C and is the copper size for a 200 A home service. 2/0 aluminum is the size for a 150 A home service.
Assumes NEC 2023 Table 310.16, 30 C ambient and no more than three current-carrying conductors. NM-B cable uses the 60 C column.
2/0 AWG specifications
| Diameter | 0.3648 in | 9.266 mm |
|---|---|---|
| Area | 133,077 cmil | 67.43 mm² |
| Copper resistance | 0.0948 ohm/1000 ft | 0.256 ohm/km |
| Aluminum resistance | 0.1561 ohm/1000 ft | 0.419 ohm/km |
| Copper weight | 402.8 lb/1000 ft | 599.5 kg/km |
| Nearest metric | 70 mm² | 70 mm² or larger |
2/0 AWG ampacity
| 60 C | 75 C | 90 C | Max breaker | |
|---|---|---|---|---|
| Copper | 145 | 175 | 195 | per table |
| Aluminum | 115 | 135 | 150 | per table |
What 2/0 gauge wire is used for
- 200 A dwelling services and main feeders in copper (NEC 310.12)
- 150 A dwelling services in aluminum
- 175 A feeders in copper at 75 C
- Inverter and battery bank cables in off-grid and marine systems
2/0 is also written 00 AWG and said "two aught". It is one size larger than 1/0.
For a 200 A home, 2/0 copper works because the dwelling rule needs only 166 A. A 200 A subpanel or commercial feeder needs the full 200 A: 3/0 copper or 250 kcmil aluminum.
Most new 200 A services are run in 4/0 aluminum instead of 2/0 copper because the aluminum costs far less for the same job.
How far can you run 2/0 gauge wire?
Longest one-way run in copper that keeps voltage drop at or below 3%, single-phase.
| Load | 120 V | 240 V |
|---|---|---|
| 80 A | 237 ft | 475 ft |
| 100 A | 190 ft | 380 ft |
| 125 A | 152 ft | 304 ft |
| 150 A | 127 ft | 253 ft |
| 175 A | 109 ft | 217 ft |
Check a run
Voltage drop on 2/0 AWG
Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate
2/0 gauge wire questions
How many amps can 2/0 wire carry?
Copper: 145 A at 60 C, 175 A at 75 C, 195 A at 90 C. Aluminum: 115, 135 and 150 A.
Is 2/0 copper good for 200 amps?
For a dwelling service or main feeder, yes, under NEC 310.12. For any other 200 A feeder, use 3/0 copper.
Is 2/0 aluminum good for 150 amps?
For a 150 A dwelling service, yes (it needs 124.5 A, and 2/0 aluminum is rated 135 A at 75 C). For a 150 A subpanel feeder, use 3/0 aluminum.
Related sizes
Convert this size: AWG to mm². All sizes: wire gauge chart. Any size and length: voltage drop calculator.