Guide / conductors

Stranded vs solid wire

Use solid for 14 to 10 AWG NM-B cable and device terminations in house wiring. Use stranded for 8 AWG and larger in conduit (the NEC requires it), for anything that moves or vibrates, and for long pulls.

Ampacity is the same for both in NEC Table 310.16. The choice is about handling and terminations, not current.

Side by side

SolidStranded
AmpacitySame as stranded (Table 310.16)Same as solid
DC resistanceSlightly lowerAbout 2% higher (NEC Chapter 9 Table 8)
FlexibilityStiff, holds its shapeFlexible, pulls easily round bends
Device screwsWraps cleanly under a screwWorks under most screws and back-wire clamps; can splay
Push-in terminalsYesNo
Vibration and movementCan work-harden and crackTolerates flexing
Sizes in racewayUp to 10 AWGRequired at 8 AWG and larger (NEC 310.3(C))
CostLowerA little higher

Where each one belongs

In a typical home, branch circuits run in 14/2, 12/2 and 10/3 NM-B cable with solid conductors, because solid wire stays put while you fold it into a box and wraps neatly round a receptacle screw.

In conduit, stranded THHN is the norm. It pulls far more easily, and the NEC requires stranding for 8 AWG and larger in a raceway, apart from a few exceptions such as bonding jumpers. Feeders, services and anything 8 AWG and up are stranded.

Anything that moves (cords, machines, vehicles, boats, solar trackers) should be stranded, and often fine-strand. Solid copper that flexes repeatedly work-hardens and can break inside the insulation, which is a fire risk you cannot see.

Terminating stranded wire

Twist the strands tight before landing them and keep every strand under the screw or in the lug. For terminals not rated for stranded wire, use a crimped ferrule or a fork or ring terminal. Torque lugs to the value on the equipment label, as NEC 110.14(D) requires.

Sizing the circuit? Use the wire size calculator or the ampacity chart; both apply to solid and stranded wire.

Stranded and solid wire questions

Does stranded wire carry more current than solid?

No. NEC Table 310.16 gives the same ampacity for solid and stranded conductors of the same size and insulation. Stranded has slightly higher DC resistance, about 2% for small sizes.

Is stranded wire allowed for house wiring?

Yes. THHN in conduit is commonly stranded, and 8 AWG and larger in a raceway must be stranded. NM-B cable in 14 to 10 AWG is usually solid because it is easier to terminate on device screws.

Can stranded wire go under a screw terminal?

Many receptacles and switches accept stranded wire under the screw or in a back-wire clamp; check the device instructions. Push-in (backstab) holes are for solid wire only.

Which is better for car audio and 12 V systems?

Stranded, and usually fine-strand. Vehicles and boats vibrate, and solid wire can crack at terminals over time.