Gauge / 4/0 AWG / 11.68 mm

4/0 gauge wire (0000 AWG)

4/0 AWG copper is rated 195 A at 60 C, 230 A at 75 C and 260 A at 90 C. Aluminum: 150 / 180 / 205 A.

4/0 AWG aluminum is the most common wire for a 200 A home service. 4/0 copper is rated 230 A at 75 C.

Assumes NEC 2023 Table 310.16, 30 C ambient and no more than three current-carrying conductors. NM-B cable uses the 60 C column.

1 tick = 1 mm 11.68 mm
4/0 AWG Copper conductor and typical insulation, drawn to scale against a millimetre ruler.

4/0 AWG specifications

Diameter0.46 in11.684 mm
Area211,600 cmil107.22 mm²
Copper resistance0.0596 ohm/1000 ft0.161 ohm/km
Aluminum resistance0.0982 ohm/1000 ft0.264 ohm/km
Copper weight640.5 lb/1000 ft953.2 kg/km
Nearest metric120 mm²120 mm² or larger
Solid conductor. Resistance per 1000 ft at 75 C, per km at 20 C. Stranded wire is about 2% higher.

4/0 AWG ampacity

60 C75 C90 CMax breaker
Copper195230260per table
Aluminum150180205per table
Amps. 60 C: NM-B, UF-B and most terminals on circuits of 100 A or less. 75 C: THHN/THWN with 75 C rated terminals. 90 C: for derating only.

What 4/0 gauge wire is used for

4/0 is also written 0000 AWG and said "four aught". It is the largest AWG size; the next size up is 250 kcmil.

A 200 A home service needs 166 A under the 83% rule, and 4/0 aluminum is rated 180 A at 75 C. A 200 A subpanel feeder needs the full 200 A, so 4/0 aluminum is too small there: use 250 kcmil aluminum or 3/0 copper.

Service cable is often sold as "4/0-4/0-4/0-2/0": two hots and a neutral in 4/0 with a 2/0 ground or neutral, depending on the cable type. Check which conductor is which before you terminate it.

How far can you run 4/0 gauge wire?

Longest one-way run in copper that keeps voltage drop at or below 3%, single-phase.

Load120 V240 V
100 A302 ft604 ft
125 A242 ft483 ft
150 A201 ft403 ft
175 A173 ft345 ft
200 A151 ft302 ft
Resistance at 75 C. Aluminum runs are about 40% shorter.

Check a run

Voltage drop on 4/0 AWG

A
V
System
Conductor

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

4/0 gauge wire questions

How many amps can 4/0 wire carry?

Copper: 195 A at 60 C, 230 A at 75 C, 260 A at 90 C. Aluminum: 150, 180 and 205 A.

Is 4/0 aluminum good for 200 amp service?

Yes, for a dwelling service or main feeder under NEC 310.12. Not for a 200 A feeder that needs full rating, where 4/0 aluminum (180 A) falls short.

What is bigger than 4/0 wire?

After 4/0 AWG, sizes are given in kcmil: 250, 300, 350, 400, 500 kcmil and up. 250 kcmil is about 18% more copper than 4/0.

Related sizes

Convert this size: AWG to mm². All sizes: wire gauge chart. Any size and length: voltage drop calculator.