Gauge / 4/0 AWG / 11.68 mm
4/0 gauge wire (0000 AWG)
4/0 AWG copper is rated 195 A at 60 C, 230 A at 75 C and 260 A at 90 C. Aluminum: 150 / 180 / 205 A.
4/0 AWG aluminum is the most common wire for a 200 A home service. 4/0 copper is rated 230 A at 75 C.
Assumes NEC 2023 Table 310.16, 30 C ambient and no more than three current-carrying conductors. NM-B cable uses the 60 C column.
4/0 AWG specifications
| Diameter | 0.46 in | 11.684 mm |
|---|---|---|
| Area | 211,600 cmil | 107.22 mm² |
| Copper resistance | 0.0596 ohm/1000 ft | 0.161 ohm/km |
| Aluminum resistance | 0.0982 ohm/1000 ft | 0.264 ohm/km |
| Copper weight | 640.5 lb/1000 ft | 953.2 kg/km |
| Nearest metric | 120 mm² | 120 mm² or larger |
4/0 AWG ampacity
| 60 C | 75 C | 90 C | Max breaker | |
|---|---|---|---|---|
| Copper | 195 | 230 | 260 | per table |
| Aluminum | 150 | 180 | 205 | per table |
What 4/0 gauge wire is used for
- 200 A dwelling services and main feeders in aluminum (NEC 310.12), often as SER or URD cable
- 175 A feeders in aluminum at full rating
- 225 A feeders in copper at 75 C
- 250 A dwelling services in copper
- Large battery banks and inverters
4/0 is also written 0000 AWG and said "four aught". It is the largest AWG size; the next size up is 250 kcmil.
A 200 A home service needs 166 A under the 83% rule, and 4/0 aluminum is rated 180 A at 75 C. A 200 A subpanel feeder needs the full 200 A, so 4/0 aluminum is too small there: use 250 kcmil aluminum or 3/0 copper.
Service cable is often sold as "4/0-4/0-4/0-2/0": two hots and a neutral in 4/0 with a 2/0 ground or neutral, depending on the cable type. Check which conductor is which before you terminate it.
How far can you run 4/0 gauge wire?
Longest one-way run in copper that keeps voltage drop at or below 3%, single-phase.
| Load | 120 V | 240 V |
|---|---|---|
| 100 A | 302 ft | 604 ft |
| 125 A | 242 ft | 483 ft |
| 150 A | 201 ft | 403 ft |
| 175 A | 173 ft | 345 ft |
| 200 A | 151 ft | 302 ft |
Check a run
Voltage drop on 4/0 AWG
Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate
4/0 gauge wire questions
How many amps can 4/0 wire carry?
Copper: 195 A at 60 C, 230 A at 75 C, 260 A at 90 C. Aluminum: 150, 180 and 205 A.
Is 4/0 aluminum good for 200 amp service?
Yes, for a dwelling service or main feeder under NEC 310.12. Not for a 200 A feeder that needs full rating, where 4/0 aluminum (180 A) falls short.
What is bigger than 4/0 wire?
After 4/0 AWG, sizes are given in kcmil: 250, 300, 350, 400, 500 kcmil and up. 250 kcmil is about 18% more copper than 4/0.
Related sizes
Convert this size: AWG to mm². All sizes: wire gauge chart. Any size and length: voltage drop calculator.