Circuit / 125 A breaker / NEC 2023
What size wire for 125 amps?
A 125 A circuit needs at least 1 AWG copper, or 2/0 AWG aluminum at 75 C.
NEC 2023, 30 C ambient, up to 3 current-carrying conductors, short run. 75 C column.
Wire size for a 125 amp breaker
| Wiring method | Material | Minimum size | Ampacity |
|---|---|---|---|
| NM-B cable (Romex) or 60 C terminals | Copper | 1/0 AWG | 125 A |
| THHN/THWN in conduit, 75 C terminals | Copper | 1 AWG | 130 A |
| 75 C terminals (XHHW, SER, USE) | Aluminum | 2/0 AWG | 135 A |
Wire size for 125 amps by distance
Copper at a full 125 A load, 3% drop, one-way distance.
How many watts on a 125 amp circuit
| Voltage | Maximum | Continuous (80%) |
|---|---|---|
| 120 V | 15,000 W | 12,000 W |
| 240 V | 30,000 W | 24,000 W |
What runs on a 125 amp circuit
- Main panels in smaller homes
- Subpanels and feeders to outbuildings
- Commercial and light industrial feeders
Over 100 A, the 75 C column applies. 1 AWG copper (130 A) or 2/0 aluminum (135 A) covers a 125 A feeder at full rating.
If the 125 A conductors are the main service or main feeder of a dwelling, the 83% rule of NEC 310.12 lets you use 2 AWG copper or 1/0 aluminum.
The equipment ground for a 125 A feeder is 6 AWG copper or 4 AWG aluminum (NEC Table 250.122).
125 A panels are a common choice for detached garages and accessory dwelling units. Feeders that long often need a size up for voltage drop: at 240 V and a full 125 A load, copper steps up to 1/0 at 200 ft and 2/0 at 250 ft to stay under 3%.
Many 125 A main breaker panels are rated for 1 AWG to 2/0 conductors at the main lugs. Check the lug range on the panel label before buying wire.
Your run
Check your 125 amp run
Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate
Permit first: most areas need a permit and inspection for a new 125 A circuit.
125 amp wire questions
What size wire for a 125 amp subpanel?
At full rating with 75 C terminations: 1 AWG copper or 2/0 aluminum. The 83% dwelling rule does not apply to subpanel feeders.
Is 1/0 aluminum good for 125 amps?
For a 125 A dwelling service or main feeder, yes. For a 125 A subpanel feeder, no: 1/0 aluminum is rated 120 A at 75 C, so use 2/0.
Other circuit sizes
Every rating on one page: wire size chart.