Circuit / 80 A breaker / NEC 2023

What size wire for 80 amps?

A 80 A circuit needs at least 3 AWG copper (or 4 AWG copper THHN when every terminal is rated 75 C), or 2 AWG aluminum at 75 C.

NEC 2023, 30 C ambient, up to 3 current-carrying conductors, short run. 60 C column by default (NEC 110.14(C)).

Wire size for a 80 amp breaker

Wiring methodMaterialMinimum sizeAmpacity
NM-B cable (Romex) or 60 C terminalsCopper3 AWG85 A
THHN/THWN in conduit, 75 C terminalsCopper4 AWG85 A
60 C terminalsAluminum1 AWG85 A
75 C terminals (XHHW, SER, USE)Aluminum2 AWG90 A
Ampacity in the column that applies.

Wire size for 80 amps by distance

Copper at a full 80 A load, 3% drop, one-way distance.

Voltage50 ft100 ft150 ft200 ft
120 V3 AWG2 AWG1/0 AWG2/0 AWG
240 V3 AWG3 AWG3 AWG2 AWG

How many watts on a 80 amp circuit

VoltageMaximumContinuous (80%)
120 V9,600 W7,680 W
240 V19,200 W15,360 W
Continuous loads (3 hours or more) are limited to 64 A.

What runs on a 80 amp circuit

With 75 C terminations, 4 AWG copper (85 A) covers 80 A. Where 60 C applies, which is the default for circuits of 100 A or less, step up to 3 AWG copper (85 A).

EV chargers are continuous loads: a charger set to 64 A needs 64 x 1.25 = 80 A of circuit. Many charger installation guides specify the wire size; follow the guide if it asks for larger.

In aluminum at 75 C, use 2 AWG (90 A).

Your run

Check your 80 amp run

A
V
System
Conductor
Max voltage drop
Wire type
Terminals rated
Hot locations and bundled wires
°C
in run

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

Permit first: most areas need a permit and inspection for a new 80 A circuit.

80 amp wire questions

Is 4 gauge wire OK for 80 amps?

Copper 4 AWG is rated 85 A at 75 C, so yes where the breaker and equipment terminals are rated 75 C. In the 60 C column it is only 70 A, so use 3 AWG copper there.

What size wire for an 80 amp EV charger circuit?

4 AWG copper with 75 C terminations, or 3 AWG copper where 60 C applies, for a 64 A charger on an 80 A breaker. Check the charger manual.

Other circuit sizes

Every rating on one page: wire size chart.