Gauge / 2 AWG / 6.54 mm
2 gauge wire
2 AWG copper is rated 95 A at 60 C, 115 A at 75 C and 130 A at 90 C. Aluminum: 75 / 90 / 100 A.
2 AWG copper is rated 115 A at 75 C. In aluminum it is the standard conductor for a 100 A dwelling service.
Assumes NEC 2023 Table 310.16, 30 C ambient and no more than three current-carrying conductors. NM-B cable uses the 60 C column.
2 AWG specifications
| Diameter | 0.2576 in | 6.544 mm |
|---|---|---|
| Area | 66,371 cmil | 33.63 mm² |
| Copper resistance | 0.19 ohm/1000 ft | 0.513 ohm/km |
| Aluminum resistance | 0.3129 ohm/1000 ft | 0.84 ohm/km |
| Copper weight | 200.9 lb/1000 ft | 299 kg/km |
| Nearest metric | 35 mm² | 35 mm² or larger |
2 AWG ampacity
| 60 C | 75 C | 90 C | Max breaker | |
|---|---|---|---|---|
| Copper | 95 | 115 | 130 | per table |
| Aluminum | 75 | 90 | 100 | per table |
What 2 gauge wire is used for
- 100 A dwelling services and main feeders in aluminum (NEC 310.12)
- 110 A feeders in copper with 75 C terminations
- 90 A feeders in aluminum
- Battery, inverter and welding cables on low-voltage DC systems
For a 100 A home service, 2 AWG aluminum works because the dwelling rule needs only 83 A, and 2 AWG aluminum is rated 90 A at 75 C. For a 100 A subpanel feeder, which needs the full 100 A, use 1 AWG aluminum or 3 AWG copper.
Searches for "2 gauge wire" also come from car audio and battery work. Those runs are sized by fuse rating and voltage drop at 12 V, and the cable is usually fine-strand welding or battery cable, not building wire.
On a 100 A feeder, 2 AWG copper gives 15 A of headroom over 3 AWG and a little less voltage drop, which helps on long runs to outbuildings.
How far can you run 2 gauge wire?
Longest one-way run in copper that keeps voltage drop at or below 3%, single-phase.
| Load | 120 V | 240 V |
|---|---|---|
| 50 A | 189 ft | 379 ft |
| 60 A | 158 ft | 316 ft |
| 70 A | 135 ft | 271 ft |
| 80 A | 118 ft | 237 ft |
| 100 A | 95 ft | 189 ft |
Check a run
Voltage drop on 2 AWG
Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate
2 gauge wire questions
How many amps can 2 gauge wire carry?
Copper: 95 A at 60 C, 115 A at 75 C, 130 A at 90 C. Aluminum: 75, 90 and 100 A.
Is 2 gauge aluminum good for 100 amps?
For a dwelling service or main feeder, yes, under the 83% rule of NEC 310.12. For a subpanel feeder at full 100 A rating, no: use 1 AWG aluminum.
What breaker for 2 AWG copper?
Up to 110 A with 75 C terminations (rated 115 A), or 90 A where 60 C terminations apply (rated 95 A).
Related sizes
Convert this size: AWG to mm². All sizes: wire gauge chart. Any size and length: voltage drop calculator.