Gauge / 2 AWG / 6.54 mm

2 gauge wire

2 AWG copper is rated 95 A at 60 C, 115 A at 75 C and 130 A at 90 C. Aluminum: 75 / 90 / 100 A.

2 AWG copper is rated 115 A at 75 C. In aluminum it is the standard conductor for a 100 A dwelling service.

Assumes NEC 2023 Table 310.16, 30 C ambient and no more than three current-carrying conductors. NM-B cable uses the 60 C column.

1 tick = 1 mm 6.54 mm
2 AWG Copper conductor and typical insulation, drawn to scale against a millimetre ruler.

2 AWG specifications

Diameter0.2576 in6.544 mm
Area66,371 cmil33.63 mm²
Copper resistance0.19 ohm/1000 ft0.513 ohm/km
Aluminum resistance0.3129 ohm/1000 ft0.84 ohm/km
Copper weight200.9 lb/1000 ft299 kg/km
Nearest metric35 mm²35 mm² or larger
Solid conductor. Resistance per 1000 ft at 75 C, per km at 20 C. Stranded wire is about 2% higher.

2 AWG ampacity

60 C75 C90 CMax breaker
Copper95115130per table
Aluminum7590100per table
Amps. 60 C: NM-B, UF-B and most terminals on circuits of 100 A or less. 75 C: THHN/THWN with 75 C rated terminals. 90 C: for derating only.

What 2 gauge wire is used for

For a 100 A home service, 2 AWG aluminum works because the dwelling rule needs only 83 A, and 2 AWG aluminum is rated 90 A at 75 C. For a 100 A subpanel feeder, which needs the full 100 A, use 1 AWG aluminum or 3 AWG copper.

Searches for "2 gauge wire" also come from car audio and battery work. Those runs are sized by fuse rating and voltage drop at 12 V, and the cable is usually fine-strand welding or battery cable, not building wire.

On a 100 A feeder, 2 AWG copper gives 15 A of headroom over 3 AWG and a little less voltage drop, which helps on long runs to outbuildings.

How far can you run 2 gauge wire?

Longest one-way run in copper that keeps voltage drop at or below 3%, single-phase.

Load120 V240 V
50 A189 ft379 ft
60 A158 ft316 ft
70 A135 ft271 ft
80 A118 ft237 ft
100 A95 ft189 ft
Resistance at 75 C. Aluminum runs are about 40% shorter.

Check a run

Voltage drop on 2 AWG

A
V
System
Conductor

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

2 gauge wire questions

How many amps can 2 gauge wire carry?

Copper: 95 A at 60 C, 115 A at 75 C, 130 A at 90 C. Aluminum: 75, 90 and 100 A.

Is 2 gauge aluminum good for 100 amps?

For a dwelling service or main feeder, yes, under the 83% rule of NEC 310.12. For a subpanel feeder at full 100 A rating, no: use 1 AWG aluminum.

What breaker for 2 AWG copper?

Up to 110 A with 75 C terminations (rated 115 A), or 90 A where 60 C terminations apply (rated 95 A).

Related sizes

Convert this size: AWG to mm². All sizes: wire gauge chart. Any size and length: voltage drop calculator.