Circuit / 70 A breaker / NEC 2023
What size wire for 70 amps?
A 70 A circuit needs at least 4 AWG copper, or 3 AWG aluminum at 75 C.
NEC 2023, 30 C ambient, up to 3 current-carrying conductors, short run. 60 C column by default (NEC 110.14(C)).
Wire size for a 70 amp breaker
| Wiring method | Material | Minimum size | Ampacity |
|---|---|---|---|
| NM-B cable (Romex) or 60 C terminals | Copper | 4 AWG | 70 A |
| THHN/THWN in conduit, 75 C terminals | Copper | 4 AWG | 85 A |
| 60 C terminals | Aluminum | 2 AWG | 75 A |
| 75 C terminals (XHHW, SER, USE) | Aluminum | 3 AWG | 75 A |
Wire size for 70 amps by distance
Copper at a full 70 A load, 3% drop, one-way distance.
How many watts on a 70 amp circuit
| Voltage | Maximum | Continuous (80%) |
|---|---|---|
| 120 V | 8,400 W | 6,720 W |
| 240 V | 16,800 W | 13,440 W |
What runs on a 70 amp circuit
- Subpanels in garages, shops and additions
- Electric furnace heat strips
- Large heat pumps per nameplate
- Feeders to detached buildings
4 AWG copper covers 70 A in both the 60 C column (70 A) and the 75 C column (85 A), so the answer is the same for NM-B cable and for THHN.
In aluminum at 75 C, use 3 AWG (75 A). 4 AWG aluminum is rated only 65 A.
A subpanel needs four wires: two hots, a neutral and an equipment ground. For a 70 A feeder, the ground is 8 AWG copper or 6 AWG aluminum (NEC Table 250.122).
70 A sits between the common 60 A and 100 A subpanel sizes. It suits a garage or workshop with a welder, a compressor and lighting, where 60 A is tight but 100 A wire would be oversized for the load calculation.
Heat pump and electric furnace nameplates often list a 70 A maximum breaker for the heat strips. Use the nameplate minimum circuit ampacity to size the wire, which can be smaller than the breaker for motor and HVAC loads.
Your run
Check your 70 amp run
Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate
Permit first: most areas need a permit and inspection for a new 70 A circuit.
70 amp wire questions
Is 6 gauge wire OK for 70 amps?
No. 6 AWG copper is rated 65 A at 75 C and 55 A at 60 C. Use 4 AWG copper.
What size aluminum wire for 70 amps?
3 AWG aluminum at 75 C (75 A). Make sure the breaker and panel lugs are rated AL/CU.
Other circuit sizes
Every rating on one page: wire size chart.