Circuit / 70 A breaker / NEC 2023

What size wire for 70 amps?

A 70 A circuit needs at least 4 AWG copper, or 3 AWG aluminum at 75 C.

NEC 2023, 30 C ambient, up to 3 current-carrying conductors, short run. 60 C column by default (NEC 110.14(C)).

Wire size for a 70 amp breaker

Wiring methodMaterialMinimum sizeAmpacity
NM-B cable (Romex) or 60 C terminalsCopper4 AWG70 A
THHN/THWN in conduit, 75 C terminalsCopper4 AWG85 A
60 C terminalsAluminum2 AWG75 A
75 C terminals (XHHW, SER, USE)Aluminum3 AWG75 A
Ampacity in the column that applies.

Wire size for 70 amps by distance

Copper at a full 70 A load, 3% drop, one-way distance.

Voltage50 ft100 ft150 ft200 ft
120 V4 AWG3 AWG1 AWG1/0 AWG
240 V4 AWG4 AWG4 AWG3 AWG

How many watts on a 70 amp circuit

VoltageMaximumContinuous (80%)
120 V8,400 W6,720 W
240 V16,800 W13,440 W
Continuous loads (3 hours or more) are limited to 56 A.

What runs on a 70 amp circuit

4 AWG copper covers 70 A in both the 60 C column (70 A) and the 75 C column (85 A), so the answer is the same for NM-B cable and for THHN.

In aluminum at 75 C, use 3 AWG (75 A). 4 AWG aluminum is rated only 65 A.

A subpanel needs four wires: two hots, a neutral and an equipment ground. For a 70 A feeder, the ground is 8 AWG copper or 6 AWG aluminum (NEC Table 250.122).

70 A sits between the common 60 A and 100 A subpanel sizes. It suits a garage or workshop with a welder, a compressor and lighting, where 60 A is tight but 100 A wire would be oversized for the load calculation.

Heat pump and electric furnace nameplates often list a 70 A maximum breaker for the heat strips. Use the nameplate minimum circuit ampacity to size the wire, which can be smaller than the breaker for motor and HVAC loads.

Your run

Check your 70 amp run

A
V
System
Conductor
Max voltage drop
Wire type
Terminals rated
Hot locations and bundled wires
°C
in run

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

Permit first: most areas need a permit and inspection for a new 70 A circuit.

70 amp wire questions

Is 6 gauge wire OK for 70 amps?

No. 6 AWG copper is rated 65 A at 75 C and 55 A at 60 C. Use 4 AWG copper.

What size aluminum wire for 70 amps?

3 AWG aluminum at 75 C (75 A). Make sure the breaker and panel lugs are rated AL/CU.