Circuit / 150 A breaker / NEC 2023
What size wire for 150 amps?
A 150 A circuit needs at least 1/0 AWG copper, or 3/0 AWG aluminum at 75 C.
NEC 2023, 30 C ambient, up to 3 current-carrying conductors, short run. 75 C column.
Wire size for a 150 amp breaker
| Wiring method | Material | Minimum size | Ampacity |
|---|---|---|---|
| NM-B cable (Romex) or 60 C terminals | Copper | 3/0 AWG | 165 A |
| THHN/THWN in conduit, 75 C terminals | Copper | 1/0 AWG | 150 A |
| 75 C terminals (XHHW, SER, USE) | Aluminum | 3/0 AWG | 155 A |
Wire size for 150 amps by distance
Copper at a full 150 A load, 3% drop, one-way distance.
How many watts on a 150 amp circuit
| Voltage | Maximum | Continuous (80%) |
|---|---|---|
| 120 V | 18,000 W | 14,400 W |
| 240 V | 36,000 W | 28,800 W |
What runs on a 150 amp circuit
- Subpanels and feeders to shops and outbuildings
- Main panels for homes with electric heat or large loads
- Commercial feeders
At full rating with 75 C terminations, a 150 A feeder needs 1/0 copper (150 A) or 3/0 aluminum (155 A).
A dwelling main service of 150 A can use the 83% rule instead: 1 AWG copper or 2/0 aluminum. See the 150 amp service page.
The equipment ground for a 150 A feeder is 6 AWG copper or 4 AWG aluminum (NEC Table 250.122).
A 150 A feeder is a typical size for a large shop, a pool house with heaters, or a second panel in a big house. In aluminum, 3/0 is the usual pick; 4/0 aluminum adds margin for voltage drop on long runs.
With 90 C conductors such as XHHW-2 or THHN in a hot attic or crowded raceway, start the derating from the 90 C column, but the final ampacity can never exceed the 75 C value at the terminals.
Sizing a main service instead? See wire size for 150 amp service, where the dwelling 83% rule applies.
Your run
Check your 150 amp run
Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate
Permit first: most areas need a permit and inspection for a new 150 A circuit.
150 amp wire questions
Is 2/0 aluminum OK for 150 amps?
For a dwelling service or main feeder, yes. For a 150 A subpanel feeder at full rating, no: 2/0 aluminum is rated 135 A, so use 3/0 aluminum.
What size copper wire for 150 amps?
1/0 copper at 75 C for a feeder at full rating, or 1 AWG copper for a dwelling main service.
Other circuit sizes
Every rating on one page: wire size chart.