Circuit / 150 A breaker / NEC 2023

What size wire for 150 amps?

A 150 A circuit needs at least 1/0 AWG copper, or 3/0 AWG aluminum at 75 C.

NEC 2023, 30 C ambient, up to 3 current-carrying conductors, short run. 75 C column.

Wire size for a 150 amp breaker

Wiring methodMaterialMinimum sizeAmpacity
NM-B cable (Romex) or 60 C terminalsCopper3/0 AWG165 A
THHN/THWN in conduit, 75 C terminalsCopper1/0 AWG150 A
75 C terminals (XHHW, SER, USE)Aluminum3/0 AWG155 A
Ampacity in the column that applies.

Wire size for 150 amps by distance

Copper at a full 150 A load, 3% drop, one-way distance.

Voltage50 ft100 ft150 ft200 ft
120 V1/0 AWG1/0 AWG3/0 AWG4/0 AWG
240 V1/0 AWG1/0 AWG1/0 AWG1/0 AWG

How many watts on a 150 amp circuit

VoltageMaximumContinuous (80%)
120 V18,000 W14,400 W
240 V36,000 W28,800 W
Continuous loads (3 hours or more) are limited to 120 A.

What runs on a 150 amp circuit

At full rating with 75 C terminations, a 150 A feeder needs 1/0 copper (150 A) or 3/0 aluminum (155 A).

A dwelling main service of 150 A can use the 83% rule instead: 1 AWG copper or 2/0 aluminum. See the 150 amp service page.

The equipment ground for a 150 A feeder is 6 AWG copper or 4 AWG aluminum (NEC Table 250.122).

A 150 A feeder is a typical size for a large shop, a pool house with heaters, or a second panel in a big house. In aluminum, 3/0 is the usual pick; 4/0 aluminum adds margin for voltage drop on long runs.

With 90 C conductors such as XHHW-2 or THHN in a hot attic or crowded raceway, start the derating from the 90 C column, but the final ampacity can never exceed the 75 C value at the terminals.

Sizing a main service instead? See wire size for 150 amp service, where the dwelling 83% rule applies.

Your run

Check your 150 amp run

A
V
System
Conductor
Max voltage drop
Wire type
Terminals rated
Hot locations and bundled wires
°C
in run

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

Permit first: most areas need a permit and inspection for a new 150 A circuit.

150 amp wire questions

Is 2/0 aluminum OK for 150 amps?

For a dwelling service or main feeder, yes. For a 150 A subpanel feeder at full rating, no: 2/0 aluminum is rated 135 A, so use 3/0 aluminum.

What size copper wire for 150 amps?

1/0 copper at 75 C for a feeder at full rating, or 1 AWG copper for a dwelling main service.

Other circuit sizes

Every rating on one page: wire size chart.