Service / 150 A / NEC 310.12

Wire size for 150 amp service

For a 150 A home service, use at least 1 AWG copper or 2/0 AWG aluminum. Where the full 150 A rating is needed, use 1/0 AWG copper or 3/0 AWG aluminum.

150 A services are common on mid-size homes and upgrades from 100 A, and the dwelling 83% rule brings the wire down a size or two.

NEC 2023 310.12 and Table 310.16, 75 C column, 30 C ambient.

150 amp service wire sizes

UseRuleCopperAluminum
Dwelling service or main feeder83% of 150 A = 124.5 A1 AWG (130 A)2/0 AWG (135 A)
Subpanel feeder, non-dwelling serviceFull 150 A1/0 AWG (150 A)3/0 AWG (155 A)
Ampacity in brackets, 75 C column. Correct for ambient temperature and conductor count where they apply.

How the 83% rule works

NEC 310.12 covers one-family dwellings and the individual units of two-family and multifamily dwellings. The service-entrance conductors, or the main feeder that carries the whole load of the unit, may have an ampacity of 83% of the service rating. For 150 A that is 124.5 A, and the smallest conductors that reach it in the 75 C column are 1 AWG copper and 2/0 AWG aluminum.

The rule reflects how homes draw power: the whole-house load almost never sits at the service rating for long. It does not change the service size itself, which still comes from a load calculation under NEC Article 220.

For a 150 A home, the conductors need 124.5 A. 1 AWG copper (130 A) and 2/0 aluminum (135 A) at 75 C both cover it.

A 150 A feeder to a subpanel, or a non-dwelling service, needs the full 150 A: 1/0 copper or 3/0 aluminum.

Grounding electrode conductor for 1 AWG copper or 2/0 aluminum service conductors: 6 AWG copper or 4 AWG aluminum (NEC Table 250.66).

Service work is for a licensed electrician. It needs a permit, an inspection and coordination with your utility, and it cannot be turned off at your own panel. Use this page to check a quote or plan an upgrade.

150 amp service questions

What size aluminum wire for 150 amp service?

2/0 aluminum for a dwelling service or main feeder under NEC 310.12. 3/0 aluminum where the full 150 A rating is needed.

What size copper wire for 150 amp service?

1 AWG copper for a dwelling service, or 1/0 copper at full rating.

Should I upgrade to 200 A instead of 150 A?

If you are adding an EV charger, heat pump or electric cooking, a load calculation under NEC Article 220 often points to 200 A. The wire cost difference is small next to doing the job twice.

Related