Service / 400 A / NEC 310.12
Wire size for 400 amp service
For a 400 A home service, use at least 400 kcmil copper or 600 kcmil aluminum. Where the full 400 A rating is needed, use 600 kcmil copper or 900 kcmil aluminum.
400 A residential services are usually built as two 200 A sections behind a 320 A continuous-rated meter, so the wire is often sized per section rather than as one 400 A set.
NEC 2023 310.12 and Table 310.16, 75 C column, 30 C ambient.
400 amp service wire sizes
| Use | Rule | Copper | Aluminum |
|---|---|---|---|
| Dwelling service or main feeder | 83% of 400 A = 332 A | 400 kcmil (335 A) | 600 kcmil (340 A) |
| Subpanel feeder, non-dwelling service | Full 400 A | 600 kcmil (420 A) | 900 kcmil (425 A) |
How the 83% rule works
NEC 310.12 covers one-family dwellings and the individual units of two-family and multifamily dwellings. The service-entrance conductors, or the main feeder that carries the whole load of the unit, may have an ampacity of 83% of the service rating. For 400 A that is 332 A, and the smallest conductors that reach it in the 75 C column are 400 kcmil copper and 600 kcmil aluminum.
The rule reflects how homes draw power: the whole-house load almost never sits at the service rating for long. It does not change the service size itself, which still comes from a load calculation under NEC Article 220.
As a single set, a 400 A dwelling service needs 332 A under the 83% rule: 400 kcmil copper or 600 kcmil aluminum. Wire this large is hard to pull and terminate, so parallel sets are common.
NEC 310.10(G) allows conductors 1/0 and larger to run in parallel. On a split 400 A meter-main with two 200 A breakers, each section is wired like a 200 A service: 2/0 copper or 4/0 aluminum per section.
Size the grounding electrode conductor from NEC Table 250.66 using the total area of the service conductors, and check the utility's service requirements, which often set the meter socket and conductor arrangement for 400 A.
Service work is for a licensed electrician. It needs a permit, an inspection and coordination with your utility, and it cannot be turned off at your own panel. Use this page to check a quote or plan an upgrade.
400 amp service questions
What size wire for 400 amp service?
As one set under the dwelling 83% rule: 400 kcmil copper or 600 kcmil aluminum. As two 200 A sections: 2/0 copper or 4/0 aluminum per section.
Is 400 A service really 320 A?
Many residential 400 A services use a meter socket rated 320 A continuous, which the utility treats as a 400 A service. The panels behind it are usually two 200 A sections.
Can I run parallel conductors for a 400 amp service?
Yes, for conductors 1/0 and larger, provided each set is the same length, material, size and insulation, and terminated the same way (NEC 310.10(G)).