Circuit / 20 A breaker / NEC 2023
What size wire for 20 amps?
A 20 A circuit needs at least 12 AWG copper, or 10 AWG aluminum at 75 C.
NEC 2023, 30 C ambient, up to 3 current-carrying conductors, short run. 60 C column by default (NEC 110.14(C)).
Wire size for a 20 amp breaker
| Wiring method | Material | Minimum size | Ampacity |
|---|---|---|---|
| NM-B cable (Romex) or 60 C terminals | Copper | 12 AWG | 20 A |
| THHN/THWN in conduit, 75 C terminals | Copper | 12 AWG | 25 A |
| 60 C terminals | Aluminum | 10 AWG | 25 A |
| 75 C terminals (XHHW, SER, USE) | Aluminum | 10 AWG | 30 A |
Wire size for 20 amps by distance
Copper at a full 20 A load, 3% drop, one-way distance.
How many watts on a 20 amp circuit
| Voltage | Maximum | Continuous (80%) |
|---|---|---|
| 120 V | 2,400 W | 1,920 W |
| 240 V | 4,800 W | 3,840 W |
What runs on a 20 amp circuit
- Kitchen countertop small-appliance circuits (required to be 20 A)
- Bathroom and laundry receptacle circuits
- Garage and workshop outlets
- Dishwashers, disposals and over-range microwaves
- 240 V baseboard heaters and mini-split heat pumps rated for 20 A
12 AWG copper is the answer for a 20 A circuit in every wiring method. 14 AWG is never allowed on a 20 A breaker, even though the 75 C column lists 20 A, because NEC 240.4(D) caps 14 AWG at 15 A.
In aluminum, 12 AWG is capped at 15 A by 240.4(D), so a 20 A aluminum circuit needs 10 AWG. Aluminum branch circuits are rare in new work.
Long runs need more copper. At a full 20 A on 120 V, 12 AWG reaches 3% drop at about 47 ft, 10 AWG at about 74 ft and 8 AWG at about 118 ft.
Your run
Check your 20 amp run
Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate
Permit first: most areas need a permit and inspection for a new 20 A circuit.
20 amp wire questions
Can I use 14 gauge wire on a 20 amp breaker?
No. NEC 240.4(D) limits 14 AWG copper to a 15 A breaker. Use 12 AWG copper for 20 A.
What size wire for a 20 amp circuit 100 feet away?
At a full 20 A on 120 V and 100 ft, 8 AWG copper gives about 2.6% drop and 10 AWG about 4%. If the real load is lighter, 10 AWG is often enough. Run your numbers in the calculator.
Other circuit sizes
Every rating on one page: wire size chart.