Gauge / 16 AWG / 1.29 mm
16 gauge wire
16 AWG copper is listed only in the 90 C column, at 18 A, and NEC 240.4(D) limits its overcurrent protection to 10 A. It is not used for 120 V branch circuits. Not listed in aluminum.
16 AWG copper is used for cords, fixture wire, speaker wire and low-voltage runs. It is too small for 120 V branch circuits in a building.
NEC 2023 Table 310.16 and 240.4(D). Cords, fixture wire and Class 2 low-voltage wiring have their own ratings in other NEC articles.
16 AWG specifications
| Diameter | 0.0508 in | 1.291 mm |
|---|---|---|
| Area | 2,583 cmil | 1.31 mm² |
| Copper resistance | 4.8834 ohm/1000 ft | 13.174 ohm/km |
| Aluminum resistance | 8.0419 ohm/1000 ft | 21.597 ohm/km |
| Copper weight | 7.8 lb/1000 ft | 11.6 kg/km |
| Nearest metric | 1.5 mm² | 1.5 mm² or larger |
16 AWG ampacity
| 60 C | 75 C | 90 C | Max breaker | |
|---|---|---|---|---|
| Copper | - | - | 18 | 10 |
| Aluminum | not listed | - | ||
What 16 gauge wire is used for
- Lamp cords and light-duty extension cords (look for the marked rating, often 13 A)
- Speaker wire for 8 ohm speakers on runs up to about 50 ft
- Fixture wire inside light fittings
- Low-voltage landscape and LED lighting on short runs
- 12 V automotive and trailer lighting circuits
Table 310.16 lists 16 AWG copper only in the 90 C column (18 A), and NEC 240.4(D) limits its overcurrent protection to 10 A, under specific conditions. In practice, building branch circuits start at 14 AWG.
Cords and fixture wires have their own ratings in NEC Article 400 and Article 402. Use the amp rating printed on the cord or the fixture listing, not Table 310.16.
On 12 V DC, 16 AWG loses voltage quickly: at 5 A it reaches 3% drop at about 7 ft one way.
How far can you run 16 gauge wire?
Longest one-way run in copper that keeps voltage drop at or below 3% on low-voltage DC circuits.
| Load | 12 V | 24 V |
|---|---|---|
| 1 A | 37 ft | 74 ft |
| 2 A | 18 ft | 37 ft |
| 3 A | 12 ft | 25 ft |
| 5 A | 7 ft | 15 ft |
| 10 A | 4 ft | 7 ft |
Check a run
Voltage drop on 16 AWG
Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate
16 gauge wire questions
How many amps can 16 gauge wire carry?
It depends on how it is used. As building wire, NEC 240.4(D) limits it to 10 A protection. As a cord, use the marked rating (often 13 A for a 16/3 extension cord). On low-voltage DC, voltage drop usually limits it first.
Can I use 16 gauge wire for a light fixture?
Inside the fixture, yes, as listed fixture wire. The circuit feeding the fixture must be at least 14 AWG on a 15 A breaker.
Is 16 gauge speaker wire good enough?
For 8 ohm speakers up to about 50 ft, yes. For 4 ohm speakers, keep 16 gauge runs under about 25 ft.
Related sizes