Gauge / 18 AWG / 1.02 mm
18 gauge wire
18 AWG copper is listed only in the 90 C column, at 14 A, and NEC 240.4(D) limits its overcurrent protection to 7 A. It is not used for 120 V branch circuits. Not listed in aluminum.
18 AWG copper is thermostat, doorbell and lamp cord wire. It belongs on low-voltage and cord work, not building branch circuits.
NEC 2023 Table 310.16 and 240.4(D). Cords, fixture wire and Class 2 low-voltage wiring have their own ratings in other NEC articles.
18 AWG specifications
| Diameter | 0.0403 in | 1.024 mm |
|---|---|---|
| Area | 1,624 cmil | 0.82 mm² |
| Copper resistance | 7.765 ohm/1000 ft | 20.948 ohm/km |
| Aluminum resistance | 12.7871 ohm/1000 ft | 34.341 ohm/km |
| Copper weight | 4.9 lb/1000 ft | 7.3 kg/km |
| Nearest metric | 0.75 mm² | 1 mm² or larger |
18 AWG ampacity
| 60 C | 75 C | 90 C | Max breaker | |
|---|---|---|---|---|
| Copper | - | - | 14 | 7 |
| Aluminum | not listed | - | ||
What 18 gauge wire is used for
- Thermostat wire (18/2 to 18/8)
- Doorbell and chime transformers
- Lamp cords (SPT-1 and SPT-2)
- Alarm, sensor and control wiring
- Fixture wire and small low-voltage LED runs
Table 310.16 lists 18 AWG copper only in the 90 C column (14 A), and NEC 240.4(D) limits its overcurrent protection to 7 A, under specific conditions.
Thermostat and doorbell circuits are Class 2 power-limited circuits fed by a small transformer, so the wire is chosen for the job and the number of conductors, not for ampacity.
On 24 V AC thermostat circuits, 18 AWG is fine for typical runs. On 12 V LED strips, check voltage drop: at 2 A, 18 AWG reaches 3% at about 12 ft one way.
How far can you run 18 gauge wire?
Longest one-way run in copper that keeps voltage drop at or below 3% on low-voltage DC circuits.
| Load | 12 V | 24 V |
|---|---|---|
| 1 A | 23 ft | 46 ft |
| 2 A | 12 ft | 23 ft |
| 3 A | 8 ft | 15 ft |
| 5 A | 5 ft | 9 ft |
| 7 A | 3 ft | 7 ft |
Check a run
Voltage drop on 18 AWG
Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate
18 gauge wire questions
How many amps can 18 gauge wire carry?
As building wire, NEC 240.4(D) limits it to 7 A protection. As a cord or fixture wire, use the marked or listed rating. On low-voltage runs, voltage drop is usually the real limit.
What gauge is thermostat wire?
18 AWG is standard for thermostat wire. The number after the slash (18/5, 18/8) is the count of conductors.
Can I use 18 gauge wire for 120 V?
Only as part of a listed cord or fixture. Never as building wire for an outlet or light circuit, which needs at least 14 AWG.
Related sizes
Convert this size: AWG to mm². All sizes: wire gauge chart. Any size and length: voltage drop calculator. Audio: speaker wire gauge chart.