Gauge / 18 AWG / 1.02 mm

18 gauge wire

18 AWG copper is listed only in the 90 C column, at 14 A, and NEC 240.4(D) limits its overcurrent protection to 7 A. It is not used for 120 V branch circuits. Not listed in aluminum.

18 AWG copper is thermostat, doorbell and lamp cord wire. It belongs on low-voltage and cord work, not building branch circuits.

NEC 2023 Table 310.16 and 240.4(D). Cords, fixture wire and Class 2 low-voltage wiring have their own ratings in other NEC articles.

1 tick = 1 mm 1.02 mm
18 AWG Copper conductor and typical insulation, drawn to scale against a millimetre ruler.

18 AWG specifications

Diameter0.0403 in1.024 mm
Area1,624 cmil0.82 mm²
Copper resistance7.765 ohm/1000 ft20.948 ohm/km
Aluminum resistance12.7871 ohm/1000 ft34.341 ohm/km
Copper weight4.9 lb/1000 ft7.3 kg/km
Nearest metric0.75 mm²1 mm² or larger
Solid conductor. Resistance per 1000 ft at 75 C, per km at 20 C. Stranded wire is about 2% higher.

18 AWG ampacity

60 C75 C90 CMax breaker
Copper--147
Aluminumnot listed-
Amps. 60 C: NM-B, UF-B and most terminals on circuits of 100 A or less. 75 C: THHN/THWN with 75 C rated terminals. 90 C: for derating only.

What 18 gauge wire is used for

Table 310.16 lists 18 AWG copper only in the 90 C column (14 A), and NEC 240.4(D) limits its overcurrent protection to 7 A, under specific conditions.

Thermostat and doorbell circuits are Class 2 power-limited circuits fed by a small transformer, so the wire is chosen for the job and the number of conductors, not for ampacity.

On 24 V AC thermostat circuits, 18 AWG is fine for typical runs. On 12 V LED strips, check voltage drop: at 2 A, 18 AWG reaches 3% at about 12 ft one way.

How far can you run 18 gauge wire?

Longest one-way run in copper that keeps voltage drop at or below 3% on low-voltage DC circuits.

Load12 V24 V
1 A23 ft46 ft
2 A12 ft23 ft
3 A8 ft15 ft
5 A5 ft9 ft
7 A3 ft7 ft
Resistance at 75 C. Aluminum runs are about 40% shorter.

Check a run

Voltage drop on 18 AWG

A
V
System
Conductor

Estimate for planning only, based on NEC 2023. Local code and the inspector decide. Have a licensed electrician check mains work. How we calculate

18 gauge wire questions

How many amps can 18 gauge wire carry?

As building wire, NEC 240.4(D) limits it to 7 A protection. As a cord or fixture wire, use the marked or listed rating. On low-voltage runs, voltage drop is usually the real limit.

What gauge is thermostat wire?

18 AWG is standard for thermostat wire. The number after the slash (18/5, 18/8) is the count of conductors.

Can I use 18 gauge wire for 120 V?

Only as part of a listed cord or fixture. Never as building wire for an outlet or light circuit, which needs at least 14 AWG.